Télécharger Imprimer la page

Tripp-Lite SmartOnline S3MX Serie Manuel Du Propriétaire page 49

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 143
6. Operation Principles
6.2.5 Bypass Mode
Upon connecting to utility input power, the UPS is in Bypass Mode before the UPS is turned on (if BYPASS setting is enabled), and charger
function will be active when battery is connected.
If the UPS has been turned on and encounters abnormal situations (over-temperature, overload, etc.), the static transfer switch will
transfer the load from the inverter to the bypass source with no interruption. If the transference was caused by a recoverable reason, the
UPS will return to Line Mode once the situation has been resolved.
Q4
Maintenance Breaker
STS
Single
Input
Rectifier
Inverter
Main
Load
Q1
Inverter
Q3
Input Breaker
Relay
Output Breaker
Battery Breaker
Q4
Maintenance Breaker
STS
Bypass
Q2
Dual
Bypass Breaker
Rectifier
Inverter
Inputs
Main
Load
Q1
Inverter
Q3
Input Breaker
Relay
Output Breaker
Battery Breaker
Bypass Mode Diagrams
49

Publicité

loading