Télécharger Imprimer la page

Tripp-Lite SmartOnline S3MX Serie Manuel Du Propriétaire page 13

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 143
3. Installation and Setup
3.5 Single UPS Installation
Installation and wiring must conform in accordance with the local electric laws/regulations. The following procedures must be performed by
a professional electrician:
1) Make sure the mains wire and breakers in the building provide adequate power for the rated UPS capacity so as to avoid electrical
shock or fire hazards.
Note: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than the UPS system's maximum input current.
Otherwise, the receptacle may be shorted and destroyed.
2) Switch off the mains in the building before installation.
3) Turn off all connected devices before connecting to the UPS.
4) Prepare the power cables according to Table 3.2. Refer to Table 3.3 for UPS Input Breaker sizes and Table 3.4 for Battery Cabinet
Batteries and Breaker sizes.
Warning:
• Before connecting any wires, make sure the AC input and battery power are completely shut off.
Table 3.2 Power Cables
Model
100KVA
120KVA
160KVA
200KVA
100kVA
100K
Q1
Input 1
+BATTERY
+BATTERY
Input(Ph)
Output(Ph)
70 mm
70 mm
2
(2/0 AWG)
(2/0 AWG)
95 mm
95 mm
2
(3/0 AWG)
(3/0 AWG)
150 mm
150 mm
2
(300 MCM)
(300 MCM)
185 mm
185 mm
2
(400 MCM)
(400 MCM)
160kVA/200kVA
160K/200K
120kVA
120K
Q3
Q4
Q1
Output
Maintenance Bypass
Input 1
+
N
-
External
External
Battery
Battery
Input/Output
Input/Output
Breaker
Breaker
+
N
-
-BATTERY
-BATTERY
Power cable (mm
and AWG)
2
Neutral
70 mm
2
2
(2/0 AWG)
95 mm
2
2
(3/0 AWG)
150 mm
2
2
(300 MCM)
185 mm
2
2
(400 MCM)
13
Battery
Ground
150 mm
70 mm
2
(300 MCM)
(2/0 AWG)
240 mm
95 mm
2
(500 MCM)
(3/0 AWG)
120 mm
x 2
150 mm
2
(4/0 AWG x 2)
(300 MCM)
185mm
x 2
185 mm
2
(400 MCM x 2)
(400 MCM)
2
2
2
2

Publicité

loading