7. UPS Operation
7.4.2 Turn Off Operation in Bypass Mode / Standby Mode (Load Will Be Dropped)
When the UPS is not turned ON or OFF, the UPS operates in the Standby Mode or Bypass Mode, depending on the Bypass Mode setting.
LCD diagrams are showing Bypass Mode disabled or Standby Mode, and Bypass Mode enabled.
Step 1: Turn off the Output Breaker (Q3).
Bypass Mode Setting is Enabled
12:00
2018/01/01
Step 2: Turn off the Input Breaker (Q1).
2018/01/01
UPS enters Shutdown Mode.
Step 3: The UPS will enter Shutdown Mode and slowly de-energize. Wait until the LCD is OFF.
Step 4: After the UPS powers off, switch OFF the external power switch to disconnect the AC power to the UPS.
Step 5: If the UPS will remain disconnected from the AC power for an extended period, switch OFF the battery breaker
(external battery cabinet).
62