6. Electrical work
I Permissible Lengths
1. Maximum line length via outdoor unit (M-NET cable):
L1+L2+L3+L4+L5 ≤ 500 m [1640 ft] (1.25 mm² [AWG16] or more)
2. Maximum transmission cable length between Branch box and outdoor unit. (M-NET cable):
L1+L2, L3+L4, L5 ≤ 200 m [656 ft] (1.25 mm² [AWG16] or more)
3. Maximum transmission cable length between branch box and outdoor unit. (A-Control cable):
L6 ≤ 25 m [82 ft] (1.5 mm² [AWG14])
4. MA Remote controller cable length:
m1 ≤ 200 m [656 ft] (0.3 to 1.25 mm² [AWG22 to AWG16])
I Constraint items
OC
(51)
TB3
TB7
M1 M2 S M1 M2 S
L
3
A
OC
(53)
TB7
L
TB3
4
M1 M2
S
M1 M2 S
Power Supply
A
Unit
M1 M2 S
System
controller
M1 M2 S
*2
Different refrigerant systems cannot be connected together.
*1.
Plural indoor units cannot be operated by a single remote controller.
*2.
M-NET remote controller cannot be connected.
TB3A
Branch Box
Branch Box
L
1
TB5
TB3B
M1
M2
S
TB3C
(01)
TB3D
L
2
TB3E
A
TB3A
Branch Box
Branch Box
TB5
TB3B
(06)
M1
M2
S
TB3C
A B
M-NET
RC
(101)
L
m
6
1
TB
TB5/TB15
1
A
S1
S1
A-IC
MA-RC
2
B
S2
S2
(01)
S3
S3
TB
TB5/TB15
A
S1
S1
A-IC
1
MA-RC
B
S2
S2
2
(02)
S3
S3
TB
TB5/TB15
S1
S1
A-IC
1
A
MA-RC
S2
S2
2
B
(03)
S3
S3
TB
S1
S1
A-IC
WL-RC
S2
S2
(04)
S3
S3
TB
S1
S1
A-IC
S2
WL-RC
S2
(05)
S3
S3
TB
TB5/TB15
S1
S1
A-IC
1
A
MA-RC
S2
S2
2
B
(06)
S3
S3
TB
TB5/TB15
S1
S1
A-IC
1
S2
S2
(07)
2
S3
S3
TB
S1
S1
A-IC
S2
WL-RC
S2
(08)
S3
S3
( ) : Address
*1
en
28

Publicité

loading

Ce manuel est également adapté pour:

Mxz-sm96taMxz-sm120ta