Télécharger Imprimer la page

Interlogix ATS125 Serie Manuel D'installation page 17

Masquer les pouces Voir aussi pour ATS125 Serie:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 21
Tx1 (ATS125x) / Tx0 (ATS1250/1260): Off if
ATS125x/1260 is not addressed or is not programmed to
be polled by the control panel.
Four-door/four-lift DGP local databus indicator LEDs:
Tx (ATS125x) / Tx1 (ATS1250/1260): Flashes when
ATS125x/1260 is polling remote devices
(readers/interfaces) on the local databus; TX should
always be active.
Rx (ATS125x) / Rx1 (ATS1250/1260): Flashing indicates
remote devices reply to polling.
Setup procedure
The minimal setup only consists of settings required to activate
the DGP and the connected RASs for programming.
1.
Set addresses of RASs (readers or keypads) connected to
the local databus of the four-door/four-lift DGP
2.
In the Advisor Master control panel, installer programming
(menu 19.4): DGP, activate polling for the four-door DGP
and set the DGP type.
How to access the ATS125x programming menu
Access to the Door programming menu is via the Advisor
Master, Installer menu 28, "To remote devices". When
programming in the four-door programming menu, you are
actually programming the ATS125x.
If you are denied access to "To remote devices", it is because
one or more of the above hardware or programming criteria
have not been met.
1.
The display shows:
Remote Device: 1-DGP, 2-RAS
Device:
Enter the type of remote device you wish to program.
Select 1 (DGP).
2.
Enter the number of the remote device you wish to
program. The DGP number is the same as the DGP
address.
Remote DGP Setup
DGP No.:
The following is briefly displayed:
Connecting...
Enter to Abort
You have now accessed the ATS125x Programming menu
for the ATS125x that you have selected. The display
shows the four-door programming menu display:
"#" –Move On
"*" Move back
Menu:
ATS125x programming menus
1-DGP Options: Global options valid for all doors of the
selected four-door/four-lift DGP.
2-Door Options: Options valid for each individual door on
the ATS125x/1260.
P/N 1070341 (ML) • REV F • ISS 16APR18
All manuals and user guides at all-guides.com
3-Initialise Database: Allows initialisation of door
database. Resets all data in the DGP to default.
4-Display Card: Displays card details on LCD for the last
card that is badged.
5-Door Groups: Allows door group details to be viewed.
6-Lift Groups: Allows ATS1260 lift group details to be
viewed.
7-System Options: Allows ATS125x/1260 outputs to be
activated to indicate system faults on ATS125x/1260.
8-Program Macro Logic: Enables outputs and internal
events to be generated by logic functions using
ATS125x/1260 events.
9-Version Number: ATS125x/1260 firmware and CPLD
version number.
10-To Local Devices: Enables you to access the remote
devices on the local databus.
Note: CARD FORMAT only can be configured via
management software.
See also Programming Map in Figure 11.
Initialise Database
Initialise the four-door/four-lift DGP on initial power up only.
This is done via menu option 3, Initialise database.
Caution:
All programming and settings will be reset to factory
defaults. Factory defaults are listed in the ATS125x/1260
programming guide.
Poll connected RASs
Go to menu 1, DGP options.
Set or select the following options:
1.
Enter RASs connected to be polled.
2.
Enter LCD RAS connected.
For more details on how to program the ATS125x four-door
DGP refer to the ATS125x Programming Guide.
Troubleshooting
ATS system data bus indicator LED's
Rx1 (ATS125x)
The yellow LED flashes to indicate polling
data is received on the system data bus from
Rx0 (ATS1250/1260)
the panel. If the LED does not flash, the
control panel is not operational or the bus is
faulty
Check that DGP is powered correctly.
Check wiring DGP data bus connections.
Tx1 (ATS125x)
The red LED flashes to indicate the DGP is
replying to polling from the control panel. If
Tx0 (ATS1250/1260)
the yellow LED flashes but the red LED does
not, the DGP is not programmed to be polled
in the control panel or has a wrong address.
Check if the DGP connected to the data
bus has correct address.
Check that the DGP is being polled
(Advisor Master control panel menu
19.4).
Four-door DGP local data bus indicator LEDs
Tx (ATS125x)
The red LED flashes when ATS125x/1260 is
polling remote devices (readers/interfaces) on
Tx1 (ATS1250/1260)
the local databus. The LED should always be
active.
17 / 66

Publicité

loading

Ce manuel est également adapté pour:

Ats1260