Télécharger Imprimer la page

Interlogix ATS125 Serie Manuel D'installation page 12

Masquer les pouces Voir aussi pour ATS125 Serie:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 21
EN: Installation Sheet
Description
This manual provides information for the following access
control data gathering panel (DGP): ATS1250, ATS1260,
ATS1251, ATS1252, ATS1253 and ATS1254. When referring
to the four-door/four-lift DGP, this can be read as any variant of
the ATS125x/ATS1260, unless specifically stated otherwise.
Table 1: List of existing four-door / four-lift DGP variants
Variant
Auxiliary
Locks
power
power
ATS1250 12 V
12 V
ATS1260 12 V
12 V
ATS1251 12 V
12 V
ATS1252 12 V
24 V * ATS1642 (big)
ATS1253 12 V
12 V
ATS1254 12 V
24 V * ATS1640 (small) 445x315x90 mm
* In case of 24 V
variant always use 2 batteries in series.
ATS125x/ATS1260 four-door/four-lift DGP
overview
Figure 1: ATS125x
(1) DIP switches (see "DIP switch settings" on page 15).
(2) RAM or IUM (optional).
(3) EPROM (factory fitted).
(4) KILL jumper: Factory default ATS125x when shorted.
(5) Battery fuse F1.
(6) Auxiliary power fuse F2.
(7) Databus 1 fuse F3.
(8) Databus 2 fuse F4.
(9) Lock power 1 fuse F5.
(10) Lock power 2 fuse F6.
(11) Siren / switch fuse F7
(12) L1–L4 LED
(13) TERM 1. Use this link to terminate the system databus.
(14) TERM 2. Use this link to terminate the local databus, connection
1 on terminal CON9.
(15) TERM 3. Use this link to terminate the local databus, connection
2 on terminal CON10.
(16) CON14 Input expander connector
(17) CON15 Output expander connecter
(18) Mains terminal
Figure 2: ATS1250/ATS1260
(1) Battery 1 fuse F1.
(2) Battery 2 fuse F2.
(3) Aux. power fuse F3.
(4) EXT readers fuse F4.
(5) AUX switchable output fuse F5.
(6) Local databus fuse F6.
(7) KILL jumper. Factory default ATS1250/1260 when shorted.
(8) EPROM (factory fitted).
(9) FLASH (factory fitted).
(10) RAM or IUM (optional).
(11) TERM 2. Use this link to terminate the system databus.
(12) DIP switches (see "DIP switch settings" on page 15).
(13) Clockout – connection to output cards. +12 V DC supply and
open collector or data outputs; for connection to output
controllers.
(14) TERM 1. Use this link to terminate the local databus.
(15) +12 V DC link for ATS1810/ATS1811/ATS1820.
(16) Mains terminal
12 / 66
All manuals and user guides at all-guides.com
Housing
Dimensions
ATS1642 (big)
480x464x160 mm
ATS1642 (big)
480x464x160 mm
ATS1642 (big)
480x464x160 mm
480x464x160 mm
ATS1640 (small) 445x315x90 mm
Connections
Table 2: ATS125x connections
Termi-
Wire
Description
nal
, 
CON1
Mains power connection
System earth (see "Earthing" on page
14).
+, −
2 x 12 V batteries, 7.2 Ah (24 V version)*
1 x 12 V battery, 7.2 Ah (12 V version)
+, −, +, −
CON2
Aux. power
S+, S− **
External siren output
+, −
CON3
Lock 1 power
+, −
Lock 2 power
CON4
NO, COM, NC
Door 1 relay
NO, COM, NC
Door 2 relay
CON5
NO, COM, NC
Door 3 relay
NO, COM, NC
Door 4 relay
0V, D+, D−
CON6
System databus and panel tamper wiring
(see "ATS system databus connection" on
page 14 for details).
T, C
Tamper switch
CON7
1, 2, 3, 4
Zone 1-4 inputs
C
Common
CON8
5, 6, 7, 8
Zone 5-8 inputs
C
Common
12V, 0V, D+, D−
CON9
Local databus to connect RASs and
DGPs (see "ATS125x/1260 local databus
and earth connection" on page 14 for
details).
12V, 0V, D+, D−
CON10
Local databus to connect RASs and
DGPs (see "ATS125x/1260 local databus
and earth connection" on page 14 for
details).
*
In case of 24 VDC variant always use two batteries in series.
**
External siren output is a supervised output. Typical EOL resistor
is 1 k.
Table 3: ATS1250/1260 connections
Terminal
Wire
, 
J1
BATT +, −
+, +, −, −
J2
SW+, SW−
S+, S− *
0V, D+, D−
J3
T, C
J4
+12V, C, NC, NO, 0V
J5
+12V, C, NC, NO, 0V
J6
+12V, C, NC, NO, 0V
J7
+12V, C, NC, NO, 0V
P/N 1070341 (ML) • REV F • ISS 16APR18
Description
Mains power connection
System earth (see "Earthing" on
page 14).
2 x 12 V batteries, 7.2 Ah
Auxiliary power output
Switchable power output
External siren output
System databus and panel
tamper wiring (see "ATS system
databus connection" on page 14
for details).
Tamper switch
Unlock relay 1 output
Unlock relay 2 output
Unlock relay 3 output
Unlock relay 4 output

Publicité

loading

Ce manuel est également adapté pour:

Ats1260