LVQD2
Structural Rough-Ins
Mounting for Standard, ADA and TAS height shown.
Points A, B and C require sufficient backing
compliant with local building codes.
WARNING Ensure bowl is completely seated in
the wall bracket and securely fastened
to the wall at point A.
33-1/2"
(851)
31-1/2"
(800)
13"
28"
(330)
(723)
max
25-1/4"
(640)
16-1/2"
(419)
Access
Panel
Bracket
CODE
A
Install (1) 3/8" wall anchor with a minimum pull-out force of 1,000 lbs. per local codes at locations shown
B
C
Install wall anchor with a minimum pull-out force of 100 lbs. per local codes at locations shown
D
S
S1
RIM HEIGHT
33-1/2"
30-1/2"
8
Wall Bracket
A
S
S
5"
(127)
B
S1
S1
C
5-1/2"
(140)
24-1/8"
(612)
27-5/8"
(701)
DESCRIPTION
Provide structural backing compliant with local building codes.
#10 Wall Anchors for Valve Bracket
#10 Wall Anchors for Soap Control Box Bracket
#10 Wall Anchors for Soap Tank Bracket (100 lb pull out force)
VERTICAL HEIGHT ADJUSTMENTS
No Adjustment
Subtract 3"
2/4/2019
of C/L. The (2) anchor bolts to the right
mounting is complete, check to ensure
the bracket is level. See Step 1: Bracket
36-1/2" (927)
C L
25" (635)
25" (635)
15"
10"
S
(381)
(254)
D
3-1/2"
6-1/2"
(89)
(165)
D
14-3/4"
9-3/4"
(375)
(248)
Bradley • 215-1843 Rev. E; ECN 18-08-023
Secure bracket to wall using min. (2)
3/8" anchor bolts to the left of C/L and
min. (2) 3/8" anchor bolts to the right
of C/L must be min. 16" apart from the
anchor bolts to the left of C/L. When
Mounting for more information.
A
S
5"
(127)
B
S1
S1
C
5-1/2"
(140)
24-1/8"
(612)
27-5/8"
(701)
FIXTURE STYLE
Standard Height, ADA, TAS and CSA
Juvenile, ADA and TAS
Installation
(mm)
13-1/8"
(333)
28-1/8"
(723)
Bottom
3/4"
of
(19)
Bracket
Access
Panel
Bracket
QTY.
2
2
4
2
4
4