PR0-PAC SYSTEM OWNER INSTALLATION MANUAL
HEAT PUMP MALFUNCTION
WARNING: ISOLATE MACHINE ELECTRICALLY BEFORE
ENTERING MACHINE OR REMOVING PANELS.
The user check list should be carried out before initiating a service call.
Do not attempt to interfere with any internal control settings as these
have been factory calibrated and sealed.
Only a competent electrician should attempt to rectify electrical supply
problems.
USER CHECK LIST PROPAC30/45/70BH/BHY
MAINS
RED
FAULT
AMBER
DEFROST
WHITE
MAINS
RED
FAULT
AMBER
DEFROST
WHITE
MAINS
RED
FAULT
AMBER
DEFROST
WHITE
RED
MAINS
AMBER
FAULT
WHITE
DEFROST
RED
MAINS
AMBER
FAULT
WHITE
DEFROST
A 12 hour delay timer is incorporated into machines, which after a power interruption or from initial start up will prevent the machine compressor(s)
from starting for a 12 hour period.
26
LAMP
UNIT DOES NOT OPERATE
Power interrupted, check mains supply, external fuses, isolator
OFF
OFF
OFF
Check unit, run/ standby switch is not set to standby
ON
OFF
Check thermostat setting. Check internal control MCB setting
OFF
Check that water and air flows are not restricted
ON
Check Soft Start if fitted. Or compressor motor starter has not tripped or
OFF
external flow switch is not made (if fitted). Check HP/LP cut out switch
and reset (red button below console thermostat. (Note On Y machines
the LP switch is Auto resetting). Check water pump etc. to restore water
OFF
flow through machine. Also check thermal overloads located in the
electric box.
FAN ON COMPRESSOR OFF
ON
Unit defrosting (normal operation, unit restarts after cycle completes).
OFF
If unit stays off check that the air temperature is not below minimum
(7-10°C for H models).
ON
UNIT OPERATES INTERMITTENTLY
ON
Check water flow is not restricted by external water flow switch (if fitted)
and that the electrical supply is adequate.
ON/OFF Check that linked in external equipment is not the cause of the fault.
ON/OFF
The refrigeration circuit can only be worked on by a competent
technician in accordance with EU517/2014.
Any sign of abnormal operation such as water dripping should be
reported immediately to an installer or Dantherm Ltd.
If in doubt or if advice required contact the Dantherm Group UK Service
Department.
Telephone +44 (0)1621 856611 (option 4)
ACTION
SD566251 ISSUE 36