INSTALLATION
INSTALLED WITH BLOWER
KIT EP63
For reduced clearances installation must comply with
NFPA 211or CAN/CSA-B365.
Alcove installation
Model 1600C-1 may be installed into an alcove having a
depth of not more than 4 feet and a height of at least 7 feet,
when using a listed double wall connector that is rated for a
minimum 12" clearance to combustible material.
The minimum clearances are as shown.
Alcove installation
1 6 "
1 6 "
1 6 "
4 f o o t m a x
Walls shall not extend from front of unit when installed
in the alcove configuration.
Stove installation
If the stove is to be installed on a
combustible floor, it must be
p l a c e d
o n
a
a p p r o v e d
non-combustible hearth pad,
t h a t e x t e n d s 8 " ( 2 0 0 m m )
beyond the stove sides and
back, and 18" (455mm) to the
front.
B
D
F
A
6
WHEN
8 4 "
I l l u s t r a t e d w i t h . 7 5 " h e a r t h p a d .
8 "
8 "
8 "
1 8 "
C
E
C
Listed single wall chimney connector
Type 1
A
FROM
B*
UNIT
C
D
FROM
E
PIPE
F
* A 18 in. Minimum clearance should be maintained
from combustible wall to the chimney connector.
Double walled connectors listed for a minimum
clearance of 12" or less from combustible materials
must be used to achieve the following clearances.
Type 2
A
FROM
B
UNIT
C
D
FROM
E
PIPE
F
Flue configuration
Horizontal
Vertical
16"
16"
10"
16"
11"
11"
25"
25"
...
18"
...
18"
Flue configuration
Horizontal
Vertical
16"
16"
10"
10"
11"
11"
25"
25"
...
16"
...
12"