INPUT REGISTERS (read only) continuation
Modbus
Input register
Address
30019
OverVoltage_Alarm_Count 16bits 0-65535 -
30020
ShortCircuit_Alarm_Count 16bits 0-65535 -
30021
Current_Alarm_Count
30022
TempPCB_Alarm_Count
30023
TempIPM_Alarm_Count
30024
FOC_Alarm_Count
30025
OpenPhase_Alarm_Count
30026
Minutos_ON
30027
Days_ON
30028
Minuts_Running
30029
Days_Running
30030
MSB_Motor_Start_Count
30031
LSB_Motor_Start_Count
HOLDING REGISTERS (read and edit)
Modbus
Holding register
Address
40002
Address
40003
Baud Rate
40004
Parity
40005
Motor_Max_Speed
40006
Motor_Min_Speed
40007
Motor_Max_Cu-
rrent
40008
FG
40009
Slave_Enable
40010
Slave_Offset
40011
AN_IN1_1V/5.5mA
40012
AN_IN1_9.5V/19mA 16bits -64000
40013
AN_IN1_Filter
40014
AN_IN2_0V/4mA
40015
AN_IN2_10V/20mA
40016
AN_IN2_Filter
40018
Set_Point_Input
40019
Modbus_Set_Point
40025
Factory_Reset
MODBUS MAP
Data
Range
Def. Observations
type
16bits 0-65535 -
16bits 0-65535 -
16bits 0-65535 -
16bits 0-65535 -
16bits 0-65535 -
16bits 0-1440
-
16bits 0-65535 -
16bits 0-1440
-
16bits 0-65535 -
16bits 0-65535 -
16bits 0-65535 -
Data
Range
Default
type
16bits 1-247
1
16bits 48: 4800
192
96: 9600
192: 19200
384: 38400
16bits 0: EVEN
0
1: ODD
2: Non parity
16bits 0-5000
Ex-factory
maximum
speed
16bits 0-5000
Ex-factory
minimum
speed
16bits 0-10000
Ex-factory
maximum
intensity
16bits 0-10
1
16bits 0: OFF
1
1: ON
16bits -20-20
0
16bits -64000
Ex-factory
maximum
speed
Ex-factory
minimum
speed
16bits 0: EVEN
1
1: LOW
2: MEDIUM
3: HIGH
16bits -64000
0
16bits -64000
0
16bits 0: EVEN
1
1: LOW
2: MEDIUM
3: HIGH
16bits 0: AN_IN1
0
1: MODBUS
16bits 0-65535
0
16bits -64000
0
(continuation)
Overvoltage alarm counter
Short circuit alarm counter
Motor current alarm counter
PCB temperature alarm counter
IPM temperature alarm counter
FOC control alarm counter
Motor phase error alarm counter
Minutes operation of powered motor
Days operation of powered motor
Minutes operation with motor running
Days operation with motor running
Motor starts MSB
Example: MSB = 2 = 2 x 65,535 = 131,070 starts + LSB
Motor starts LSB
Example: LSB = 1000 = 1,000 starts + MSB
Observations
Modbus Channel/Direction
Bus speed
Parity
Maximum motor speed. Values outside the ex-factory limits or
lower than Holding register 40006 are not accepted
Minimum motor speed. Values outside the ex-factory limits or
higher than Holding register 40005 are not accepted
Maximum motor intensity (mA), doesn't accept values higher
than the ex-factory limit
Tachometer pulses
Slave function to control a second fan
Offset of the slave setpoint with respect to the setpoint (%)
Equivalence in real units of 1V or 5.5mA with respect to input IN1
Note: Only used for constant power, constant torque, PI, Proportio-
nal and Min/Max operating modes
Equivalence in real units of 9.5V or 19mA with respect to input
IN1
Note: Only used for constant power, constant torque, PI, Proportio-
nal and Min/Max operating modes
Degree of fi ltration of input IN1. A high degree favours progres-
sive changes in fan speed
Equivalence in real units of 0V or 4mA with respect to input IN2
Equivalence in real units of 10V or 20mA with respect to input
IN2
Degree of fi ltration of input IN2. A high degree favours progres-
sive changes in fan speed
Setpoint control
Setpoint via Modbus, units according to Holding register 40017
operating mode
Note: If holding registers 40011 and 40012 are not completed, the
units will be mV
Write 1234 to reset motor and return to factory settings
Note: By factory values we mean the limits corresponding to the maxi-
mum performances, constant speed operating mode and adjustment
via IN1. If the unit came with a special confi guration, this will be lost
7