Terminal
Function/Technical specifi cation
L, N, Ground
Supply voltage 230V±10% 50/60Hz
NO
Status relay, open with internal error and/or motor stopped
COM
Status relay, shared connection (2A, 30VDC / 230VAC)
NC
Status relay, closed with internal error and/or motor stopped
24V, EN
Remote ON/OFF; bridge between terminals, motor ON; by default from factory
GND
Ground reference for control
IN2
Sensor input, 0-10V or 4-20mA
24V
Voltage output, 24VDC (100mA)
OUT
Slave output, 0-10V (5mA)
D0
Modbus RTU (RS485)
D1
Modbus RTU (RS485)
FG
Hall Output (1 pulse/rev.)
IN1
0-10V / 4-20mA / PWM
10V
+10VDC (10mA)
Jumper
Function/Technical specifi cation
J5.1
Selection of input IN1, 0-10V/4-20mA sensor, open by default (0-10V)
J5.2
Selection of input IN2, 0-10V/4-20mA sensor, open by default (0-10V)
J5.3
Final selection Modbus network, open by default
J6
Selection of internal tachometer output (referenced to 10V), open by default
Fuse
Function/Technical specifi cation
F1
Final protection against general failure of electronic protections (5x20, 10A Fast)