Check on the rating plate of the rotary actuator whether the
indicated voltage corresponds with the mains voltage.
Cables with a diameter of 7 to 12 mm are permitted for the
electrical installation. The utilized cables must have an upper
limit temperature of at least 80 °C.
Use only ATEX- Approved cables and cable
Preparatory work:
Remove stainless steel screws 3 for the hood 2 and carefully
remove the hood.
8.2.1.
earth connection on outside or
inside
The earthing cable for the power supply and control must be attached
with the earthing screw 16 (M5) to the outer housing (see Figs. 1
and 2).
Procedure:
Loosen earthing screw 16 and attach eyelet of the earthing cable
to the earthing screw.
Optionally the earthing screw can be connected to Pos. A of the
power supply card.
To do this, loosen earthing screw and attach eyelet of the earthing
cable with the earthing screw.
All manuals and user guides at all-guides.com
Type 3004
Installation
bushings.
8.2.2.
multivolt or 24 V ac/Dc standard
version
The power supply voltage of the actuator is 24 V AC/DC or
100 – 240 V AC (120 – 350 V DC).
Always observe the specifications on the rating plate!
H
A
B
Fig. 16:
Power supply card for actuators with 20 - 150 Nm
english
G
F
C
D
E
21