Table with limit values for short-circuit currents for fuses according to DIN VDE 0636 characteristics gL:
Nominal current
during
6A
10A
16A
25A
40A
63A
100A
AC Voltage VAC
Range
0...300V
Mains Frequency f
Range
10..200Hz
Contact voltage detection:
UL= ........................................................25V
UL= 50V..................................................50V
*For large mains voltage fluctuations during measurements, the measurement error may increase.
Auto power off: ......................................after approx. 5 min.
Power supply: ........................................1x9V block, 6LR61
current consumtiom: ..............................approx. 20mA
Battery life:..............................................at average usage, approx. 1 year
Fuse: ......................................................1A / 250V slow blow 5x20mmI
Dimensions (LxWxH): ............................235x103x70mm (without plug)
Weight: ..................................................500g incl batterie
Environmental conditions:
Relative humidity: ..................................max 80%, non condensing
Overvoltage category: ............................CAT III / 300V to ground
Pollution degree: ....................................2
Protective class / degree: ........................II / IP50
Height above MSL:..................................up to 2000m
Temperature ranges (operating): ............0°C ... 40°C
Temperature ranges (storage): ..............-20°C ... +70°C
12 month Warranty
UNITEST instruments are subject to strict quality control. However, should the instrument function improperly
during daily use, your are protected by our 12 months warranty (valid only with invoice). We will repair free of
charge any defects in workmanship or material, provided the instrument is returned unopened and untampe-
red i.e. with undamaged warranty label. Any damage due to dropping or incorrect handling are not covered by
the warranty. If the instrument shows failure following expiration of warranty, our service department can offer
you a quick and economical repair.
Min. display for safe tripping
5s (in Amps)
32
53
81
135
228
414
714
Resolution
Tolerance
1V
±(1% rdg. +3 Digit)
Resolution
Tolerance
0,1 Hz
±(1% rdg. +2 Digit)
Min. display for safe tripping
during 0.2s (in Amps)
67
110
163
312
490
979
-
Overload Protection
400V / RI = 1 MW
Overload Protection
400V / RI = 1 MW
25V
-5% /+15%
-5% /+15%
Subject to change without notice!
Warranty
35