Data
Boiler category
Type of Gas
Maximum Input 0-2000 Ft
Maximum Input 2000-4500 Ft
Minimum Input 0-2000 Ft
Minimum Input 2000-4500 Ft
Max Inlet Gas Pressure
Min Inlet Gas Pressure
Manifold gas pressure Max input
Manifold gas pressure Min input
D.O.E Heating Capacity
Net AHRI Output
Electrical input
MAWP WATER
MAX. WATER TEMP.
Type of Gas
Maximum Input LP 0-2000 Ft
Minimum Input LP 0-2000 Ft
Maximum Input LP 2000-4500 Ft
Minimum Input LP 2000-4500 Ft
EN
12 - RATINGS AND CAPACITIES
Unit
CHB100
Category I-III
Natural gas
Btu/hr
100000
kW
29.3
Btu/hr
90000
kW
26.4
Btu/hr
31500
kW
9.3
Btu/hr
28300
kW
8.3
"wc
10.5
kPa
2.61
"wc
3.5
kPa
0.87
"wc
5.22
kPa
1.3
"wc
0.59
kPa
0.15
Btu/hr
85000
kW
24.9
Btu/hr
73000
kW
21.4
A
120V/60Hz/<12A
mm
1.35
PSI
43.5
°F
195°F
LP
Btu/hr
100000
kW
29.3
Btu/hr
36000
kW
10.6
Btu/hr
90000
kW
26.4
Btu/hr
36000
kW
10.6
34
CHB130
Category I-III
Natural gas
130000
38.2
117000
34.3
43500
12.8
39000
11.5
10.5
2.61
3.5
0.87
4.82
1.2
0.59
0.15
110000
32.2
96000
28.1
120V/60Hz/<12A
1.35
43.5
195°F
LP
130000
38.2
49000
14.4
117000
34.3
49000
14.4
CHB150
Category I-III
Natural gas
150000
44.0
135000
39.6
50000
14.7
45000
13.2
10.5
2.61
3.5
0.87
5.22
1.3
0.6
0.15
127000
37.2
110000
32.2
120V/60Hz/<12A
1.35
43.5
230°F
LP
150000
44.0
55500
16.3
135000
39.6
55500
16.3