MYCOMFORT LARGE
ESTRO
Instructions for installation:
-
Use the adhesive sensor holder provided.
Fig. 32 Fan coil unit without mount
Fig. 33: Fan coil unit with mount
Fig. 34: FU fan coil unit with front intake
EN
HUMIDITY PROBE INSTALLATION
Humidity probe is an optional accessory.
WARNING:
To prevent disturbance and consequent malfunctions, make sure that the sensor cables
are NOT situated in proximity to power lines (230V).
Should an extension be necessary, use a shielded cable to be connected to ground
only on the controller side.
Usable only in combination with a remote temperature probe, to which it must be clamped.
WATER SENSOR INSTALLATION
Water sensor (white) is an optional accessory.
Connect the water SW sensor to the remote control using the cable supplied as ac-
cessory. In case of extensions use shielded cable only.
The shielding should be connected to the ground on the fan coil side only.
The probe cable (1.5 m) can be cut to measure if necessary. Never place it near
power supply cables.
FLAT - ESTRO
Instructions for installation:
Use the special copper holder for the water sensor and position it as described below,
depending on the type of installation. Fan coil units for:
-
2 PIPE SYSTEMS – W/O VALVE : the sensor must be positioned on the heat
exchanger (figure 35).
-
4 PIPE SYSTEMS – W/O VALVES : the water sensor must be positioned on the
exchanger of the heating circuit (figure 36).
-
2 PIPE SYSTEMS – WITH VALVE : the water sensor must be positioned at the
valve inlet, on the branch coming from the system (figure 37).
-
4 PIPE SYSTEMS – WITH VALVES : the water sensor must be positioned at the
heating valve inlet, on the branch coming from the circuit (figure 38).
FC66002638 - rev. 08
È severamente vietata la riproduzione anche parziale di questo manuale / All copying, even partial, of this manual is strictly forbidden
UTN
Instructions for installation:
-
Water sensor for
4 pipe systems
WARNING:
-
-
PWN
Instructions for installation:
-
Clamp
WARNING:
-
-
50
Ex: Valves mounted on left side:
air
In the case of valveless UTN units for two-pipe systems, the water sensor must
be positioned on the pipe at the exchanger inlet.
In the case of valveless UTN units for four-pipe systems, the water sensor must
be positioned on the pipe at the heating circuit exchanger inlet.
Ex: Valves mounted on left side:
In the case of valveless PWN units for two-pipe systems, the water sensor must
be positioned on the pipe at the exchanger inlet.
In the case of valveless PWN units for four-pipe systems, the water sensor must
be positioned on the pipe at the heating circuit exchanger inlet.
air
Water sensor
for 2 pipe sys-
tems
System pipe to
be provided by
the user