3.2.2
System bus wiring (CAN)
Schematic diagram
-V
H310_004
A
Bus device 1
1
•
Only connect terminals of the same signal type.
•
Features of the signal cable:
Total cable length
Cab e type
Cable type
Cable resistance
Capacitance per unit length
•
Connection of bus terminating resistors:
•
One 120 Ω resistor at both the first and last bus device
Features:
•
CAN-based with bus protocol to CANopen (CAL-based communication profile DS301)
•
Bus length:
– 25 m at max. 1 Mbit/s data transfer rate
– up to 1 km at reduced data transfer rate
•
Very reliable data transfer (Hamming distance = 6)
•
Signal level to ISO 11898
•
Up to 63 bus participants possible
L
A
(H310)
1
CAN-
Shield
CAN+ N.C.
CG LO HI
120
A
2
up to 300 m
LIYCY 2 x 2 x 0.5 mm
twisted in pairs with shielding
Pair 1: CAN-LOW (LO) and CAN-HIGH (HI)
Pair 2: 2 GND
≤ 40 Ω /km
≤ 130 nF/km
EDBEPM-H310 DE/EN/FR 2.0
Installation
A
2
CG LO HI
Bus device 2
300 to 1000 m
2
CYPIMF 2 x 2 x 0.5 mm
≤ 40 Ω /km
≤ 60 nF/km
A
n
CG LO HI
CG LO
HI
120
A
Bus device n
n
2