Single Installation
Water Inlet
Pressure
Relief Valve
Drain Pan
4. Install the Steam Generator
WARNING: Risk of property damage. Allow a minimum of 12" (305 mm) of air space around the
steam generator at all times. This provides an area for the heat generated by the unit to dissipate.
NOTICE: For optimum performance, install the steam generator as close as possible to the steam head.
The steam generator must be installed within 25' (7.62 m) of the steam head.
Install the desired drain pan at the steam generator location. Kohler Co. recommends using a
KOHLER drain pan.
1230488-2-B
Control
Cable
Input
Steam Outlet
Drain (install per
applicable codes.)
Maintain a 12" (305 mm)
minimum space around
the units.
12" (305 mm)