3-WIRE & 2-WIRE CENTRIPRO 1Ø MOTOR WIRE
3-WIRE & 2-WIRE CENTRIPRO 1Ø MOTOR WIRE
SIZING CHART
SIZING CHART
Based on Service Factor Amps, 30º C Ambient and 5% Voltage Drop
Motor Rating
Volts
HP
kW
115
½
0.37
230
½
0.37
230
¾
0.55
230
1
0.75
230
1.1
Based on Service Factor Amps, 30º C Ambient and 5% Voltage Drop
Motor Rating
Volts
HP
kW
115
½
0.37
230
½
0.37
230
¾
0.55
230
1
0.75
230
1.1
Tables based on values from NEC, Tables 310.16 and 310.17 and NEC, Chapter 9, Table 8 Conductor Properties.
NOTE: Motors and control boxes are designed to operate on 230V systems. Systems with low line voltage,
between 200 – 207 volts require the next larger cable size than shown in the 230V charts. If using a
3-wire motor with control box on a low voltage application switch to a 208V start relay. The 208V start
relay order numbers are found on control box repair part charts in this manual.
Another option is to use a boost transformer to increase voltage.
The 2-wire sizing chart above is only for use with PSC type, 2-wire motors.
Temperature Conversions:
20º C = 68º F, 30º C = 86º F, 60º C = 140º F, 75º C = 167º F, 90º C = 194º F
PUMPSAVER 235
PUMPSAVER 235
GND
L2
L1
FUSED DISCONNECT
OR CIRCUIT BREAKER
L1
CT1
L1
L2
CT
PRESSURE SWITCH
OR
OTHER CONTROL
SW
L1
L2
YEL BLK RED
DELUXE CONTROL BOX
14
Motor Lead Lengths - CentriPro 2-Wire Motors -
60º C & 75º C Insulation - AWG Copper Wire Size
SFA
14
12
10
9.5
115
183
293
4.7
466
742 1183 1874 2915 4648 7379 11733 14803 18688 23544
6.4
342
545
869
9.1
241
383
611
11.0
199
317
505
Motor Lead Lengths - CentriPro 3-Wire Motors (CSIR) -
60º C & 75º C Insulation - AWG Copper Wire Size
SFA
14
12
10
12.6
87
138
221
6.3
348
553
883
8.3
264
420
670
9.7
226
359
573
11.1
197
314
501
PUMP
CT2
L2 IN L2 OUT
PUMP
MOTOR
8
6
4
463
721
1150 1825 2902 3662 4623 5824
1376 2141 3413 5419 8617 10871 13724 17290
968
1506 2400 3811 6060 7646 9652 12160
801
1246 1986 3153 5013 6325 7985 10060
8
6
4
349
544
867 1376 2188 2761 3485 4391
1398 2175 3467 5505 8753 11044 13942 17564
1061 1651 2632 4178 6644 8383 10582 13332
908
1413 2252 3575 5685 7173 9055 11408
793
1234 1968 3124 4968 6268 7913 9969
PUMPSAVER 111 / 233
PUMPSAVER 111 / 233
GND
L1
L2
FUSED DISCONNECT
OR CIRCUIT BREAKER
L1
L2
PRESSURE
SWITCH
OR OTHER
CONTROL
GND
PRESSURE SWITCH MAY BE INSTALLED
AHEAD OF THE PUMPSAVER WHEN
RAPID CYCLE PROTECTION IS
NOT REQUIRED
2
1/0
2/0
3/0
2
1/0
2/0
3/0
PUMPSAVER
111 / 233
L1
L1
L2
IN
OUT
IN
L1
L2
GND
L1
PRESSURE SWITCH
OR OTHER CONTROL
L1
TO MOTOR OR CONTROL BOX
4/0
4/0
L2
OUT
L2
GND
L2
GND