Ambient probe correction (OFFTR)
Using this parameter it is possible to correct, and therefore calibrate, the temperature read by the ambient probe
integrated into the Comando Remoto.
Parameter
OFFTR
The value can be corrected in 0.1°C steps.
Weather compensation (CL EN)
Using this parameter it is possible to enable (setting it to 1) weather compensation.
Parameter
CL EN
If the parameter is set to 0, weather compensation is disabled. In this case the setpoint sent to the boiler card is the
CH SL value.
Activation of ambient probe integrated into the Comando Remoto (AMBON)
If the CL EN parameter is set to 1, the value set in the AMBON parameter is ignored. If the AMBON parameter is set
to 0 and CL EN to 0, the Comando Remoto manages the boiler flow setpoint directly (CH SL).
Parameter
AMBON
Min.
Max.
-3°C
+3°C
Min.
Max.
0
1
Min.
Max.
0
1
cod. 3542A990 - Rev 01 - 03/2022
Default value
0°C
Default value
1
Default value
1
81