of the gate reverse in case of impact against objects or persons in
accordance with the current EN standards (always use the right tool to
ensure compliance with the values imposed by the standard), without
special adjustments on the control panel, as it operates using special
internal software.
If the power sensor is used in opening or closing (only in high-speed) and
then again, in the opposite direction, the gate stops and then reverses for
1 second.
The alarm status will be displayed by the blinker which will remain active for
one minute, during which time you can restore gate operation by pressing
any command button.
FUNCTIONING IN DEAD MAN MODE WHEN THE SAFETY DEVICES
ARE FAILING
If the safety edge fails or remains engaged for more than 5 seconds, or
if photocell fails or remain engaded for more than 60 seconds, the open,
close, k button and pedestrian commands will work only in dead man mode.
The signal that this mode has been activated is given by the blinking of the
programming led.
With the blinking of the programming led, the opening and closing operation
are allowed only with the command button pressed and held. The radio
commands and that of automatic closing, will be excluded, since their use
in this mode, is not allowed by the norms.
Once the failing safety device is repaired, in automatic after 1 second, all
standard commands that were selected, such as step by step, automatic
mode, radio commands and automatic closing start functioning again.
Note 1: during this functioning in dead man mode, in case of damage to
the safety strips (or photocells) the photocells (or safety strips) still
work by interrupting the operation in progress.
Note 2: the stop command is not to be considered a safety command
that can be bypassed in this mode. Therefore, when pressed or
damaged, it will not allow any movement of the gate.
The dead-man operation is only an emergency operation which must
be activated for a very short period and with the complete installation
at sight so to have a secure and safe control of the system. As soon
as possible however, the failing safety devices must be repaired and
activated.
BLINKER
PRE-BLINKING
DIP 5 - OFF => the motor and blinker begin simultaneously.
DIP 5 - ON => the blinker begins 3 seconds before the motor.
GATE OPEN WARNING LIGHT (COM-SIGNAL)
Signals when the gate is open, partially open or not closed completely.
Turns off only when the gate is completely closed.
This signal is active during programming.
N.B.: Max 3 W. If push buttons or lamps are in excess, the control panel
processes will be endangered and possibly halt operation.
OPERATION AFTER A BLACK-OUT (WITHOUT BATTERIES)
When the power supply comes back the DL1 led turns on and remains on
for all the time the gate stays open. The led will turn off only once the gate
is completely closed.
It is recommended to fully open the gate. Let the gate close by itself
or with automatic closing, or wait until the blinker stops flashing before
commanding it to close.
This will allow the gate to realign. If, motors were released and moved from
the normal position when closed during the blackout, the first movement
after power returns must be complete.
If the black out occurs when the gate is still moving or when the gate is
open and the first command sent after the black out is a closing command,
the closing of the gate will be carried out with a total delay between the
two gate leaves. Therefore, first the leaf M2 will close completely; once it is
off, M1 will start closing. This separate movement of the two gate leaves is
done to avoid their incorrect overlapping.
16
All manuals and user guides at all-guides.com
TECHNICAL SPECIFICATIONS
- Temperature range
- Humidity
- Voltage
- Frequency
- Battery power
- Transformer Power
- Maximum absorption
- Network Micro-switches
- Maximum power gate open indicator
- Maximum blinker power
- Power available for photocells and accessories 1A ± 15%
- Power available for radio connector
RADIO SPECIFICATIONS
- Receiving Frequency
- Impedance
- Sensitivity
- Pick-up time
- Drop time
- All inputs must be used as clean contacts because the power is generated
internally (secure power) to the board and is set up to ensure compliance
with double or reinforced insulation with regard to dangerous voltage.
- Any external circuits connected to the outputs of the control panel must be
made in such a manner as to ensure compliance with double or reinforced
insulation with regard to dangerous voltage.
- All inputs are controlled by a programmed integrated circuit that performs
a self check every time it starts operating.
0 ÷ 55 °C
<95% without
condensation
230 V~ ± 10 %
(120 V / 60 Hz upon
request)
50/60 Hz
20-24 Vdc
130 VA -
primary 230 Vac
secondary 18 Vac
50 mA
100 ms
24 Vdc 3 W (equivalent
to one 3 W or 5 LED
light bulb with resistor in
series at 2.2 KΩ)
24 Vdc 20 W
200Ma
433,92 MHz
52 Ω
>2,24 µV
300 ms
300 ms
EN