and to the minimum current (min Isc) that is needed to determine the maximum length of the
line protected. The protection against short-circuit must operate on the line before any thermal
and electrothermal effects of the overcurrents may damage the cable and relevant connections.
During the electrical installation take particular care to respect the phase rotation. The
terminal boards for cables connection are positioned at the front of the UPS, under the
breakers. To access the terminals remove the front protection, extracting the fixing bolts.
Mains connection
The connection to the mains must be carried out with protection fuses between the
mains and the UPS.
The use of differential protection devices in the line supplying the UPS is
unadvisable. The leakage current to ground due to the RFI filters is rather high
and it can cause spurious tripping of the protection device.
According to CEI EN62040-1 standard, in order to take into account the UPS'
leakage current, residual current devices having adjustable threshold can be used.
Power (kVA)
Input Fuses (A)
Input cables
2
(mm
)
Ground cables
Output cables
Battery cables
26
OMD10073 REV. D
Installation and start-up of UPS Keor Hp 60-160kVA
Installation et démarrage de l'UPS Keor Hp 60-160 kVA
Installazione e avviamento UPS Keor Hp 60-160kVA
Electrical connection data
Rectifier
Bypass
Rectifier
Bypass
2
(mm
)
2
(mm
)
2
(mm
)
60
80
100
3x125
3x150
3x200
3x150
3x200
3x315
3x35
3x50
3x70
4x35
4x50
4x70
16
25
35
4x35
4x50
4x70
2x35
4x50
4x70
125
160
3x250
3x315
3x315
3x400
4x95
3x120
4x95
4x120
50
70
4x95
4x120
2x95
2x120