installation planning
EN
2.3
installation option 3 - rear opening
Installation Option 3 (rear opening) requires an air outlet opening to be framed no more than 1.5" below the
enclosure top to avoid trapping heat in the upper areas and centered on the appliance center. Minimum air outlet
opening dimension must be followed. The opening is required. Framing the rear opening lower will overheat
the appliance, the enclosure, and fi nishing material.
Dynamic Heat
Control™ rear air
outlet opening must
be located out of
reach of the user.
Opening must not
be restricted by fur-
nishings or decor.
Air outlet opening is required to be centered with the appliance.
WARNING
!
When using a rear air outlet opening,
it is critical that the adjoining room or
living spaces are in direct air communi-
cation (i.e. of an open plan confi guration
or connected by a permanently open
doorway or archway). This prevents
the appliance from being in a negative
pressure more than that of the adjoining
room. Failure to follow these require-
ments can result in reversing the Dy-
namic Heat Control™ air fl ow and will
cause the appliance, safety barrier, and
fi nishing materials to overheat, creating
a fi re hazard.
note:
Increasing the air outlet opening will allow the appliance, the barrier, the temperatures on the surfaces above the fi replace opening, and
the enclosure be at cooler temperatures. It will also allow the air to circulate more effectively in the room. However, if the appliance
is equipped with the Dynamic Heat Control™ Plus, then the opening size must be 80 sq. in. for models LV38-1, LV50-2,
LVX38(-1), and LVX50(-1), or 160 sq. in. for models LV62, LV74, LVX62(-1), and LVX74(-1).
6
W415-2373 / B / 04.30.21
Suitable for Dynamic Heat Control™ Plus
(Q x R)*
S
Room 1
Access
Side of
fi replace
AIR OUTLET
OPENING IS HOT
WHEN APPLIANCE
IS OPERATING!
Room 2
ceiling
0-1.5" Max.
enclosure top
must be installed
2 1/2"
Other
min.
room
2-3"
6" min.
Wall mounted
object (picture
frame, appli-
ance, etc.)
ALTERNATIVE