things, arches must have inspection openings for the chimney sweep and be properly
insulated against condensation. The line should not be longer than 4 m and not have
more than 3 bends. If the line leads outdoors, it should be provided with a suitable
windbreak and fly screen.
General information on the subject of room air dependent or room air independ-
ent operation:
The stove is supplied as a standard room air-dependent fireplace stove. This means
that the stove draws all of the combustion air from the installation room via the central
air intake on the back. A sufficient supply of combustion air (at full load approx. 25m³ /
h) is absolutely necessary.
In combination with ventilation and air conditioning systems (e.g., controlled ventilation
systems, fume hoods, etc.), Section 4 of the Firing Ordinance (FeuVO) is decisive in
Germany. The flue gas routing must be monitored by special safety devices (e.g., via
an approved differential pressure monitor) or, if a ventilation system is used, this must
ensure that no negative pressures greater than 4 Pa occur in the installation room com-
pared to the outside and that the necessary combustion air (approx. 25 m3 / h) for the
fireplace.
Please always observe - in consultation with your authorized district chimney sweep -
the applicable local regulations and rules. We cannot accept any liability for changes
made after this manual has been printed. We reserve the right to change without notice.
The above-mentioned safety devices are not a substitute for professional planning and
design of an adequate combustion air supply.
As part of the acceptance, the district chimney sweep must check the adequate com-
bustion air supply / overall installation.
2.6 Choice of flue gas and air connection placement
The following steps must be observed when converting the flue gas connection:
Pic. 5
Pic. 6
1- Detach the rear panel of the device by unscrewing the 6 screws (pic 6). Then lift
and remove the back panel.
29