Accessories - Empire Heating Systems FAW-55-1SPP Instructions Pour L'installation Et Manuel Du Propriétaire

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Model No. FAW-55 may be vented as shown. The vent cap must
be at least 12 feet (3.7m) above the floor. Clearance to combus-
tible construction is held by the fixed spacers at 1 inch (25mm)
with B-1 vent pipe. Installation must conform to local codes.
4" (102mm) Round (all parts purchase locally except in item 2)
1. Type B-1 round pipe
2. Part No. DV-648, 4" (102mm) oval-to-round flue adapter kit
(see accessories)
3. Single story type B-1 gas vents require a baseplate and one
pair of ceiling plate spacers.
4. Multi-story type B-1 gas vents require a baseplate, one pair
of ceiling plate spacers at the first floor ceiling and one pair of
fire stop spacers at each successive ceiling level.
4" (102mm) Oval (all parts purchase locally)
1. Type B-1 oval pipe
2. Single story type B01 gas vents require a baseplate and one
pair of ceiling plate spacers.
3. Multi-story type B-1 gas vents require a baseplate, one pair
of ceiling plate spacers at the first floor ceiling and one pair of
fire stop spacers at each successive ceiling level.
4" (102mm) Oval In-The-Wall (wall parts purchase locally)
1. Type B-1 oval pipe
2. Type B01 oval elbows
3. Single story type B-1 gas vents require a baseplate and one
pair of ceiling plate spacers.
4. Multi-story type B-1 gas vents require a baseplate, one pair
of ceiling plate spacers at the first floor ceiling and one pair of
fire stop spacers at each successive ceiling level.
Stud space around gas vents must be free of obstructions and
building paper.

Accessories

Part No.
SOR-1
Register, side outlet, fixed register
SOK-1
Side outlet, 10" (254mm) maximum extension,
fixed register
ROK-1
Rear Outlet, 10" (254mm) maximum extension,
adjustable register
DV-651
Vent enclosure, 14" (356mm) [for rooms up to 96
1/2" (245cm) in height]
DV-655
Vent enclosure, 24" (610mm) [for rooms up to 106
1/2" (270.5cm) in height]
DV-666
Vent enclosure, 36" (914mm) [for rooms up to 118
1/2" (301cm) in height]
DV-648
4" (102mm) Oval-to-Round flue adapter kit
Page 12
All manuals and user guides at all-guides.com
Description
Use U.L. listed gas vent equipment when installing the FAW-55. For
vent pipe running through walls, roof, and within one (1) inch (25mm)
of combustible construction, use B01 [one inch (25mm) clearance
to combustibles] vent pipe. Type B-2 x 4 or Type B-2 x 6 are to be
used in conjunction with a Listed fire stop spacer.
Type BW gas vent pipe is available for single story or multi-story
installations, Type BW gas vent pie is to be used with the Listed
base plate, ceiling plate spacers and fire stop spacers.
32192-1-0314

Publicité

Table des Matières
loading

Table des Matières