Mounting of AC supply connector
The AC input must be made using a WAGO connector type WINSTA reference770-103.
Remarks:
The shore power unit integrated chargers work as soon as they are powered on (input cable connected, powered and
main circuit breaker Q01 closed).
Integrated chargers stop as soon as they are not under voltage (disconnected from AC network or Q01 input main
breaker opened).

3.2.3 AC distribution cable

The cross-section of the 2, 3 or 4 wire distribution (depending on model) must be 2,5mm². The installer should define
the type of cable (H07-VK, MX...) according to the type of application and the applicable standards.
The current in the cable must not exceed 10A.
Always use cable markers with insulating collars in accordance with installation standards governing AC network input
connections.
The PE conductor (commonly called "earth", the green and yellow wire) of the AC source must be connected to the
terminal provided for the purpose, and this must be done before connecting any other terminals (earth bar).
The neutral cable must be connected to the output terminal "N" of the circuit breaker.
The phase cable must be connected to the other output terminal of the circuit breaker.
31