Service
- Troubleshooting
Fault diagnosis and repair
In the event of a malfunction, first check
that the prerequisites for correct
operation are fu llfilled:
1. Is the system connected to the
power supply?
2. Is there oil in the tank?
3. are all shut-off valves open?
4. Are all control and safety devices,
such as the boiler thermostat, low
water level detector, limit switch,
etc. adjusted correctly?
If the malfunction persists, use the
following table.
It is not permitted to repair any
Red blink code of
signal lamp (LED))
2 blinks
3 blinks
4 blinks
5 blinks
6 blinks
7 blinks
8 blinks
9 blinks
10 blinks
420010602200
components relevant to safety.
These components must be
replaced by parts with the same
WARNING
order number.
Only use original spare parts.
WARNING
In the event the burner stops, in
order to preventany damage to
the installation, do not unblock
WARNING
the burner more than twice in a row. If
the burner locks for a third time, con-
tact the customer service.
Error code table
«AL» at
Possible cause
term. 10
on
No establishment of flame at the end of «TSA»
- Faulty or soiled fuel valves - Faulty or soiled flame detector
- Poor adjustment of burner, no fuel - Faulty ignition equipment
on
Free
on
Extraneous light on burner startup
on
Free
on
Free
on
Too many losses of flame during operation
(limitation of the number of repetitions)- Faulty or soiled fuel valves.
- Faulty or soiled flame detector - Poor adjustment of burner.
on
Time supervision oil preheater
- Oil preheater failed 5 times during prepurging
on
Free
off
Wiring fault or internal fault, output contacts,other faults.
on
3 times temporary fault of the output contacts
NB: after each operation:
• under normal operating conditions
(doors closed, hood fitted, etc.), check
combustion and check the individual
lines for leaks.
• Record the results in the relevant
documents.