Function
- Oil burner pump
SUNTEC E
The heavy oil burner pump used is a self-
priming gear pump, which must be
connected as two-line pump via a bleed
filter. There is an intake filter and an oil
pressure regulator integrated in the pump.
Pressure gauges for pressure
measurements and negative pressure
TECHNICAL DATA
General
Mounting
Flange mounting according to EN 225.
Connection threads
Cylindrical according to ISO 228/1
Inlet and return
G 1/2"
Nozzle outlet
G 1/4"
Pressure gauge port
G 1/8"
Vacuum gauge port
G 1/2"
Valve function
Pressure regulating - no cut-off
Filter
Open area: 45 cm
²
Opening size
Shaft
Ø 11mm according to EN 225.
By-pass plug
Inserted in return port for 2 pipe system
to be removed with a 3/16" Allen key
for 1 pipe system
.
Weight
4
kg
Hydraulic data
Nozzle pressure range
14 - 30 bar
Delivery pressure setting
20 bar
Operating viscosity
3 - 75 cSt
Oil temperature
0 - 130°C max. nella pompa
installation to light oil :
I
nlet pressure
vacuum to prevent air separation from oil.
installation to heavy oil : 3,5 bar m
Return pressure
installation to light oil : 3,5 bar max.
installation to heavy oil : 3,5 bar max.
Rated speed
3600 gpm max.
Torque (to 40 gpm)
0,3 N.m
Choice of heater
Crtridge
Ø 12 mm
Fitting
in accordo con EN 50262
Rating
50-80 W
LINE Electrical supply
BV... Fuel valve
FS
Flame signal
M
Burner motor
OW Release contact of oil preheater
W
Control thermostat or pressurestat
Z
Ignition transformer
420010602200
1
suction intake connection.
2
return connection.
3
oil pressure gauge connection.
4
negative pressure gauge connection.
5
oil pressure regulator.
6
pressure connection
measurements must be connected before
the equipment is commissioned.
NB: before starting the burner, check that
the return pipe is open. An eventual
obstraction could damage the pump
sealing device.
Capacity (L/h)
Capacity (L/h)
;
Viscosity
=
Data shown take into account a wear margin.
Do not oversize the pump when selecting the
gear capacity.
0,45 bars max.
a
x.
1 No voltage
2 Power supply on, no heat request
3 Heat request: pre-heater ON
4 Preventilation: motor ON, ignition ON
4' Parasitic flame monitoring
5 Burner start: solenoid valve OFF, flame
production, safety time
Pump capacity
Pressure (bar)
Pressure (bar)
200 cSt
20 cSt
Rated speed
gpm
5 cS
= 2850
PUMP
IDENTIFICATION
(Not all model combinations are available
Consult your Suntec representative)
Pressure regulation
Gear set capacity
(see pump capacity curves)
Shaft rotation
and nozzle location
(seen from shaft end)
(vista lato albero)
A : clockwise rotation/
right hand nozzle.
C: anti clockwise rotation/
left hand nozzle. izquierdo
E
4
N
C
1
069
Flange mounting
body with
069 :
preheater cavity
model without cut-off function
Revision number
Installation
P : by-pass plug installed in return port
for two-pipe operation
Oil under suction
Inlet
Oil under pressure
By-passed oil
returned to tank,
or to suction
Tenuta
TWO PIPE
albero
INSTALLATION
Pressure
adjustment
By-pass
plug
inserted
Back
Return
to suction
ONE PIPE
Return
INSTALLATION
plugged
6 Flame present, post-ignition period
7 Burner operation
8 End of heat request, solenoid valve
closes, burner stop
9 Standby
www.ecoflam-burners.com
EN
Filter
7 P
Vacuum
gauge port
Gear set
By-pass hole
To nozzle
Pressure
gauge port
By-pass