XA00090D
Terminal assignment and
connection data, power
supply
Terminal assignment and
connection data for signal
circuits with limited power
24
Terminal assignment and connection data
all Transmitter
Designation
Functional values
!
Note!
The following tables contain values/specifications, which are dependent on the type code (type of
measuring device). Please compare the following type code to the one shown on the nameplate of your
measuring device. A graphic representation of the electrical connections can be found on Page 23.
Terminal assignment of transmitter 65***-*...*H, 65I-*...*H
Transmitter
20 (+)
Assignment
–
Electric circuit
–
Safety-related
–
values
Functional
–
values
Terminal assignment of transmitter 65***-*...*K, 65I-*...*K
Transmitter
20 (+)
Assignment
–
Electric circuit
–
Safety-related
–
values
Functional
–
values
L1 (L+) 1
Supply voltage
(as per nameplate)
AC: U = 20 to 53 V; 14 VA
DC: U = 16 to 62 V; 8W
Terminal no. (inputs/outputs)
21 (–)
22 (+)
23 (–)
–
–
–
–
Terminal no. (inputs/outputs)
21 (–)
22 (+)
23 (–)
–
–
–
–
Proline t-mass 65
N (L–) 2
Protective earth
Caution!
Observe the grounding
scheme of the system!
24 (+)
25 (–)
26 (+)
PROFIBUS PA
–
PA +
–
EEx nA II or
EEx nL IIC
–
U
i
I
i
P
i
L
i
C
i
FNICO
–
galvanically isolated,
U
Bus
I
Bus
IEC 61158-2 (MBP)
24 (+)
25 (–)
26 (+)
FOUNDATION
Fieldbus
–
FF +
–
EEx nA II or
EEx nL IIC
–
U
i
I
i
P
i
L
i
C
i
FNICO
–
galvanically isolated,
U
Bus
I
Bus
IEC 61158-2 (MBP)
Endress+Hauser
*
27 (–)
PA –
35 V DC
600 mA
8.5 W
10 H
5 nF
Field device
9 to 32 V DC
11 mA
27 (–)
FF –
35 V DC
600 mA
8.5 W
10 H
5 nF
Field device
9 to 32 V DC
12 mA