ELECTRICAL CONNECTION
The appliance is equipped with an electrical cable having an European plug. The electric
•
cable has to be connected to a socket 1N 230V AC 50Hz and it hasn't to touch any warm
or sharp surfaces of the appliance.
The appliance should be connected with a grounding system
•
COMBUSTION AIR INTAKE DIRECT FROM ENVIRONMENT
It's advisable to read, follow and respect what indicated in Normative and prescriptions.
•
The equipment should have the necessary air for combustion, supplied by external air
•
intake.
The air intake should have the following characteristics :
•
a)
Total free section min 200 cm²;
b)
Connected directly with installation environment ;
c)
Protected with grate or lath ( attention to not reduce the min. section required on
point a ) and placed so that to avoid obstruction.
The air inflow can be also supplied from the adjacent room but the air intake should be
•
always free and connecter ahead outside. No chimney or suction hood should be present
in the environment of installation or into the nears ones.
Inside the adjacent room the air intake should have the characteristics required in letter a
•
and c .
The adjacent room can not be use as garage, warehouse of combustible material etc..
•
INSTALLATION REDUCER FLOW
If the pipe for combustion air is not DIRECTLY connected to the outside, through a
•
special pipe, it's necessary to insert the "reducer flow" into the combustion air inlet duct
Please go on with following instructions:
•
Take out the "reducer flow"
•
from the envelope included
with the appliance..
Locate in the back part of the
•
equipment, the combustion air
inlet in which the "reducer
flow" has to be inserted.
Insert completely the "reducer
•
flow" into the combustion air
inlet pipe.
IT IT IT IT- - - - GB
GB- - - - FR
FR- - - - ES
ES mod. 502-502X-502L-502LX