Fault finding guide
Important!
Fault finding
More help
30
All manuals and user guides at all-guides.com
If the dehumidifier is not functioning correctly, shut it down immediately!
Use this table to localize and solve a possible problem or fault:
Fault
Possible cause
-
• The dehumidi-
fier does not
work
• no light in the
LEDs on the
display
The compressor
• The compressor
has stopped auto-
does not work
matically caused by
• the triangle is
a too high tempera-
constantly red
ture on the con-
denser
-
• The dehumidi-
fier does not
work
• the lighting on
the display is
green
If you cannot find the reason for the fault, switch off the unit immediately in order to pre-
vent further damage.
Contact a service technician or a Dantherm Air Handling representative.
Solution
• Check the external fuses
• Check the power supply to the unit
If the unit does not start again after 45
minutes, check the following:
• Check that the fan(s) is running
• Check if the filter in the duct kit is dir-
ty
• Check if the condenser coil is dirty
• Check if the room temperature is
higher than 36 °C. If the room tem-
perature is higher than 36 °C, the
unit must be stopped
• Check that the duct openings are not
covered
Check the built-in or the external hygro-
stat, if any, by setting it to a low relative
humidity, e.g. 10 – 20 %RH.
If the unit still does not start, check the
built-in or external hygrostat for defects