mundoclima MUPR-09-H7 Manuel D'installation page 118

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Indoor Unit Error Display
Display
Operation lamp
E0
☆ 1 time
E1
☆ 2 times
E3
☆ 4 times
E4
☆ 5 times
E5
☆ 6 times
EC
☆ 7 times
F0
☆ 1 times
F1
☆ 2 times
F2
☆ 3 times
F3
☆ 4 times
F4
☆ 5 times
F5
☆ 6 times
P0
☆ 1 times
P1
☆ 2 times
P2
☆ 3 times
P4
☆ 5 times
Timer lamp
X
Indoor unit EEPROM parameter error
X
Indoor / outdoor units communication error
X
Indoor fan speed has been out of control
X
Indoor room temperature sensor T1 open circuit or short circuit
X
Evaporator coil temperature sensor T2 open circuit or short circuit
X
Refrigerant leakage detection
O
Overload current protection
O
Outdoor ambient temperature sensor T4 open circuit or short circuit
O
Condenser coil temperature sensor T3 open circuit or short circuit
O
Compressor discharge temperature sensor T5 open circuit or short circuit
O
Outdoor unit EEPROM parameter error
O
Outdoor fan speed has been out of control
IPM malfunction or IGBT over-strong current protection
Over voltage or over low voltage protection
High temperature protection of compressor top diagnosis and solution
Inverter compressor drive error
118
Description

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Mupr-12-h7Mupr-18-h7Mupr-24-h7

Table des Matières