Dimplex HPL 6S-TUW Instructions D'installation Et D'utilisation page 25

Masquer les pouces Voir aussi pour HPL 6S-TUW:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

HPL 6S-TU(R)W
7
Complies with the European safety regulations
8
Additional model features
8.1
Type of defrosting
8.2
Frost protection, condensate tray /
Water in device protected against freezing
8.3
Maximum operating pressure (heat sink)
2
9
Heat output COP
9.1
Heat output / COP
10
Cooling capacity / COP
10.1 Cooling capacity / COP
1. For air temperatures between -22°C and -5°C, flow temperature increasing from 45? to 60?.
2. These data indicate the size and capacity of the system according to EN 14511. For an analysis of the economic and energy efficiency of the system, other parameters, in particular
the defrosting capacity and regulation, should also be taken into consideration. These figures are only achieved with clean heat exchangers. Instructions for care, commissioning
and operation can be found in the relevant sections of the installation and operation instructions. The specified values have the following meaning, e.g. A7/W35: outside air tem-
perature 7 °C and heating water flow temperature 35 °C.
3. The heat output and COP is reduced by approx. 5 % in lower operation
4. The maximum sound power level under full load can increase by up to 5 dB(A).
5. The specified sound pressure level represents the free sound area level. The measured value can deviate by up to 16 dB(A), depending on the installation location.
6. See CE declaration of conformity
7. The heat circulating pump and the heat pump manager must always be ready for operation.
www.gdts.one
7
at A-7 / W35
at A2 / W35
at A7 / W35
at A7 / W45
at A10 / W35
2 4
at A27 / W18
at A27 / W7
at A35 / W18
at A35 / W7
452163.66.68 · FD 9908
6
Reverse circulation
Yes
bar
3.0
EN 14511
kW / ---
3.9 / 2.9
kW / ---
5.0 / 3.9
kW / ---
6.3 / 4.7
kW / ---
5.9 / 3.5
kW / ---
6.6 / 4.7
EN 14511
kW / ---
-
kW / ---
-
kW / ---
-
kW / ---
-
English
6
Reverse circulation
Yes
3.0
3.9 / 2.9
5.0 / 3.9
6.3 / 4.7
5.9 / 3.5
6.6 / 4.7
5.5 / 3.8
3.7 / 2.7
4.9 / 3.0
3.6 / 2.3
EN-11

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Hpl 6s-turwHwk 332econ5s

Table des Matières