Tightening Torque - Weidmüller Klippon STB Consignes De Montage

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 23

Tightening torque

Tightening torque lid screws:
Tightening torque earth stud:
Tightening torque earth stud inside: 7.5 Nm
Tightening torque slide nut inside: 2.5 Nm
Fitting Cable Glands
The ingress protection rating (IP6x) that is stated on the certification label
must be maintained.
The enclosure may be supplied complete with cable entries. Where the
installer drills cable entries, they must be installed in accordance to the
areas/limitations as specified on the certified drawings and in accordance
with the enclosure certificate.
Where adjacent cable entries are installed, sufficient clearance must be
maintained to allow the fitting of sealing/retaining washers and the rotation
of the cable gland hexagons.
If site drilling takes place, carefully remove any drilling debris, particularly
debris that is close to sealing areas. Take care that the material does
not become overheated and that there is no visible deformation of the
enclosure. For the installation of cable glands it is necessary to follow the
guidelines as stated in the instructions issued by the manufacturer.
Earthing and Bonding
The Klippon
STB enclosures are fitted with an internal / external M6 earth
®
stud as standard.
It is important when providing protective wiring that the correct size of
conductor is used and that this is connected to a suitably sized earth stud.
The following table details the size of cable that is required for a variety of
applications.
6
2.5 Nm
7.5 Nm