FX2N Series Programmable Controllers
ENG
*1 Internal 24V DC
*2 FX
-10PG inputs and outputs need to be
2N
supplied from external power supply. For
power consampution of the input and output,
please see FX
*3 FX
series PLC cannot connect together
2N
with an FX
A n F X
2 N
attached to an FX
an FX
-16CCL-M module. Only one FX
2N
32ASI- M module can be connected to the
PLC.
*4 Maximum number of I/O points per system
Connection is allowed as far as the following
condition is satisfied:
(Actual nu mb er of I/O points of PLC) +
(Num be r of p oints occu pied by sp e cial
exte n s io n blo ck s ) + (N u mb e r o f po i nt s
occupied by FX
Number of remote I/O modules) ≤ 256
Moreover, if connecting two or more FX
1 6C CL -M, the firs t ma s te r mo d ule c a n
connect to the "remote I/O modules" and
"remote device modules" but subsequent
modules can only connect to "remote device
modules".
FRE
*1 24 V CC interne
*2 Les entrées et sorties du FX2N-10PG doivent
être alimentés avec une tension externe. Des
indications sur la consommation des entrées
et sorties sont mentionnées dans le manuel
du FX2N-10PG.
*3 Dans un API de la série FX2N, aucun FX2N-
32ASI-M ne peut être exploité ensemble avec
un FX2N-16CCL-M. Un FX2N-32ASI-M ne
peut pas être raccordé à un API de la série
FX2N, dans lequel un FX2N-16CCL-M est
utilisé. Seul un FX2N-32ASI-M peut être
raccordé.
*4 Le nombre maximal d'adresses E/S par
système peut être utilisé tant que la condition
suivante est satisfaite : (Nombre E/S de
l'a ppa re il de base) + (No mbre E/S de s
a p p a r e i l s d ' ex t e n s i o n e t d e s m o d u l e s
spéciaux) + (Nombre d'adresses qui sont
affectées par FX2N-16CCL-M : 8) + (32 x
nombre de modules E/S décentralisés) ≤ 256
Lors d'utilisation de plusieurs FX2N-16CCL-
M, le 1er module maître peut être relié avec
le s " mo du le s E /S d éc e ntra lisés" e t le s
"appareils décentralisés" mais les autres
F X 2 N - 1 6 C C L - M s e u l e m e n t a v e c l e s
"appareils décentralisés".
-10PG User's Manual.
2N
-32ASI-M and FX
-16CCL-M.
2N
2N
- 3 2 A S I - M m o d u l e c a n n o t b e
series PLC that is using
2N
-16CCL-M: 8) + (32 x
2 N
*5 The value depends on the switch setting (16,
32, 48, 64, 96 or 128 points). However, the
number of connected master blocks can be
arbitrary as far as the total number of I/O
p o i n t s o f a b a s i c u n i t , m a s t e r bl o c k s,
extension units/ blocks and special extension
units/blocks (occupying eight input or output
points) is equal to 256 points or less.
*6 For details, refer to the FX
Manual.
-
2N
*7 For details, refer to the FX
Manual.
*8 The I/O control points of both the FX
32ASI-M and PLC CPU must not exceed 256
points. Therefore, there is a limitation in the
number of units (number of slaves) which can
be controlled according to the I/O points
recognized by the PLC's CPU (occupation).
Occupation I/O points: Each AS- i slave
station occupies 4 CPU I/ O points.
-
2N
*9 FX
the AS-interface power supply.
*5 La valeur dépend du réglage du commutateur
(16, 32, 48, 64, 96 ou 128 adr.). Le nombre de
modules maîtres pouvant être installés est
toutefois limité par la plage d'adresse de l'UC.
La somme des adresses E/S de l'appareil de
base, des appareils d'extension, des modules
maîtres et des modules spéciaux (affectant 8
entrées et sorties) ne doit pas être supérieure
à 256.
*6 Pour en savoir davantage consultez le Manule
de l'Utilisateur FX2N-64CL-M.
*7 Pour en savoir davantage consultez le Manule
de l'Utilisateur FX2N-64CL-M.
*8 La somme des adresses E/S du FX2N-
32ASI-M et de l'UC de l'API ne doit pas
dépasser 256. Ainsi, il y a une limitation du
nombre d'unités (nombre d'esclaves) qui
peuvent être raccordées et reconnues par
l'UC. Ad re ss e s E /S a ffe c té e s : c h aq u e
module esclave AS-i affecte 4 entrées et 4
sorties.
*9 Le FX2N-32ASI-M est alimenté en tension via
un module d'alimentation AS-I externe et
consomme 70 mA.
Introduction 1
-64CL-M User's
2N
-64CL-M User's
2N
-32ASI-M must be supplied 70mA from
2N
1-6
-