Wiring
3.5
Connection check
After the electrical installation of the device, always perform the following final checks:
Device condition and specification
Are the device or the cables damaged (visual check)?
Electrical connection
Is the cable/conduit installation correctly separated, with no loops or crossovers?
Are the cables' load relieved?
Have the cables been correctly connected? Compare with the
connection schematic on the terminals or see Fig. 3.
Are all terminal screws tightened?
Is the cable or conduit entry sealed?
Is the housing cover screwed tight?
28
TMT142 HART®
Hint
-
Hint
-
-
See connection schematic on
the housing
Visual check