Commissioning
Pos. no.
Function
4
Measured value display
(0.81" / 20.5 mm character size)
5
Status and information display
6
Display "Communication"
7
Display "Configuration locked"
4.3.2 Local operation, setup of the hardware
Fig. 6: Hardware setup using jumpers J1, J2 and J3
ESD - electrostatic discharge.
Protect the terminals from electrostatic discharge. Failure to observe this may result in
destruction or malfunction of parts of the electronics.
Jumpers J1, J2 and J3 for the hardware setup can be found on the electronics module. In order
to set the jumper, open the device cover and if applicable pull off the display.
30
Description
Measured value display. If a warning is present this display
alternates between the measured value and the warning code.
In the event of an error, the error code is dispalyed instead of
the measured value.
Display of which value is being indicated on the display. On PV
a customer specific text can be entered. On warning, the
display shows the warning code as well as "WARN". On faults
the display shows "ALARM".
The communication icon appears on read or write access using
the HART
If the software or hardware setup/configuration is locked, the
"Configuration locked" icon appears.
J3
TRANSMITTER SECURITY
FAIL MODE
ON
LO
OFF
HI
J1
J2
®
protocol.
TMT142 HART®
A0026196