9.0 Specifications

table 25: General Specifications
Phase
Frequency
Output Voltage Regulation
Output Harmonic Distortion
Efficiency
Noise Reduction
Minimum Loading
Voltage Surge Suppression
Ambient Temperature
Humidity
Directives
Certifications
UL 1012, CSA C22.2 No. 107.1
Warranty
Single
60 Hz
±3% for an input line variation of +10% to -20%
Less than 3% total RMS content at full load
Up to 92% at full load (typical) – model dependent
Common mode noise rejection exceeds 120 dB; Transverse noise rejection exceeds 60 dB
40%
Meets ANSI/IEEE C62.41 Category A & B waveforms (formerly IEEE 587-1980)
Operating: -20°C to +50°C; Storage: -20°C to +85°C
<95% non-condensing
RoHS compliant
Model
63-23-112-4
63-23-612-8
63-23-125-4
63-23-625-8
63-23-150-8
63-23-650-8
63-23-175-8
63-23-210-8
63-23-210-C8
63-23-710-8
63-23-215-8
63-23-215-C8
63-23-220-8
63-23-220-C8
63-23-720-8
63-23-230-8
63-23-230-C8
63-23-730-8
63-23-250-8
63-23-250-C8
63-23-750-8
63-28-775-8
63-28-810-8
63-28-815-8
63-28-275-8
63-28-310-8
63-28-315-8
63-29-250-8
63-29-275-8
63-29-310-8
63-29-315-8
63-31-150-8
63-32-210-8
63-32-220-8
63-32-230-8
10 year limited warranty
MCR Hardwired Series – 50 Hz & 60 Hz
A272-282 Rev. 4 02/2020
50 Hz
±5% for an input line variation of +10% to -20%
Certification
cULus
cULus
cULus
cULus
cULus
cULus
cULus
UL
cULus
cULus
UL
cULus
UL
cULus
cULus
UL
cULus
cULus
UL
cULus
cULus
cULus
cULus
cULus
UL
UL
UL
CSA
CSA
CSA
CSA
cULus
cULus
cULus
cULus