MCR Hardwired Series – 50 Hz & 60 Hz
A272-282 Rev. 4 02/2020
table 23: Fusing & Wiring
Required Circuit Protection/Minimum Gauge for 90°C Wire
Input Voltage
Catalog
Number
110–120
63-23-612-8
3 A/1,0 mm
63-23-625-8
6 A/1,0 mm
63-23-650-8
10 A/1,5 mm
63-23-710-8
15 A/2,5 mm
63-23-720-8
30 A/6,0 mm
63-23-730-8
45 A/16,0 mm
63-23-750-8
80 A/25,0 mm
63-28-775-8
---
63-28-810-8
---
63-28-815-8
---
Page: 16
220–240
1,5 A/1,0 mm
2
2
3 A/1,0 mm
2
2
6 A/1,0 mm
2
2
10 A/1,5 mm
2
2
15 A/2,5 mm
2
2
25 A/4,0 mm
2
2
40 A/10,0 mm
2
2
60 A/16,0 mm
2
80 A/25,0 mm
2
110 A/50,0 mm
2
Minimum Gauge for 90°C Wire
Output Voltage
380–415
110–120
0,8 A/1,0 mm
2
1 A/1,0 mm
2
3 A/1,0 mm
2
6 A/1,0 mm
2
10 A/1,5 mm
2
15 A/2,5 mm
2
20 A/4,0 mm
16,0 mm
2
30 A/6,0 mm
25,0 mm
2
40 A/10,0 mm
35,0 mm
2
60 A/16,0 mm
45,0 mm
2
220–240
1,0 mm
1,0 mm
1,0 mm
1,0 mm
1,0 mm
1,0 mm
1,5 mm
1,0 mm
4,0 mm
1,5 mm
6,0 mm
2,5 mm
4,0 mm
10,0 mm
16,0 mm