MCR Hardwired Series – 50 Hz & 60 Hz
A272-282 Rev. 4 02/2020
For Catalog numbers 63-31-150-8, 63-32-210-8, 63-32-220-8, & 63-32-230-8
table 12: electrical Connections—Figure 7
Catalog Number
63-31-150-8
63-32-210-8
63-32-220-8
63-32-230-8
table 13: Product Parameters
Catalog Number
63-31-150-8
63-32-210-8
63-32-220-8
63-32-230-8
table 14: Fusing & Wiring
Required Circuit Protection/Minimum Gauge for 90°C Wire
Input Voltage
Catalog
Number
95–130
63-31-150-8
---
63-32-210-8
---
63-32-220-8
---
63-32-230-8
---
Page: 12
FIGURe 7
Primary Voltage
600
Secondary Voltage
120
208
240
VA
500
1000
2000
3000
175–235
190–260
380–520
---
---
---
---
---
---
---
---
---
---
---
---
60 Hz
Connect Lines to
H1 and H2
Connect Lines to
X1 and X2 OR X3 and X2
X4 and X5
X1 and X3
BTU Output at Full load, +40°C Ambient
280
519
1229
1331
Minimum Gauge for 90°C Wire
Output Voltage
475–650
120
2 A/14 AWG
14 AWG
3 A/14 AWG
14 AWG
10 A/14 AWG
10 AWG
15 A/12 AWG
8 AWG
208
240
14 AWG
12 AWG