Settings and use of the transmitter
Configuration
It is possible to set the measuring ranges and the unit of the instrument either
by switch and/or via software.
To configure the transmitter, it must not be energized. Then, you
can make the settings required, with the DIP switches (as shown
on the drawing below).When the transmitter is configured, you can
power it up.
Please follow carefully the combinations beside with the DIP switch.
If the combination is wrongly done, the following message will
appear on the display of the transmitter "CONF ERROR". In that
case, you will have to unplug the transmitter, place the DIP switches
correctly, and then power the transmitter up.
Units setting – active switch
Outputs setting – active switch
To set a unit of measurement, put the on-off
To set an output, put the on-off switches 1, 2 and 3 of the
switch 4 of the units as shown below.
measuring ranges as shown below.
Configurations
°C
°F
to +50 °C
1
1
1
1
2
2
2
2
Combinations
3
3
3
3
4
4
4
4
Configuration via LCC-S software (option)
It is possible to configure intermediate ranges, an offset...
Example: for a 0-100 °C transmitter, minimum delta is 20 °C.
The instrument can be configured from 0 to +20 °C or from
-10 to +10 °C. In order to compensate a possible drift of the
sensor, it is possible to add an offset to the displayed value
by the TH 110 transmitter: it shows 48% RH, a standard
instrument shows 45% RH. It is then possible, via the
software, to integrate an offset of -3 to the displayed value by
the TH 110 instrument.
The configuration of the parameters can be done either with the DIP switch or via software (you can not
combine both solutions).
Mounting
To mount the transmitter, mount the ABS plate on the wall
(drilling: Ø 6 mm, screws and pins are supplied).
Insert the transmitter on the fixing plate (see A on the drawing beside).
Rotate the housing in clockwise direction until you hear a "click" which
confirms that the transmitter is correctly installed.
Maintenance: please avoid any aggressive
Precautions for use: please always use the device
solvent. Please protect the transmitter
in accordance with its intended use and within
and its probes from any cleaning product
parameters described in the technical features in order
containing formalin, that may be used for
not to compromise the protection ensured by the
cleaning rooms or ducts.
device.
Active switch
On-off switch
1
2
Output setting
3
Unit setting
4
Off
On
From 0
From -20
From -50
From 0 to
to +80 °C
to +50 °C
+100 °C
1
1
1
2
2
2
3
3
3
4
4
4
PC configuration
1
Please refer to the
user manual of the
Connect the cable
2
LCC-S software
of the LCC-S to the
3
to make the
connection of the
4
configuration.
transmitter.
Active switch (S1)
75 mm
37.5 mm
40 mm
8 mm
A
A
4.5 mm
14 mm
A
A
7.5 mm
Guide rapide
Français
Température d'utilisation, protection de l'instrument et information stockage
Conditions d'utilisation (°C/%RH/m): de -10 à +50 °C. En condition de non condensation. De 0 à 2000 m.
Protection: IP65
ou IP20
(2)
(1)
Température de stockage: de -10 à +70 °C.
Dimensions
112 mm
46 mm
90 mm
46 mm
112 mm
Modèle arrière
41 mm
90 mm
41 mm
90 mm
46 mm
90 mm
Modèle déporté
Symboles utilisés
Pour votre sécurité et afin d'éviter tout endommagement de l'appareil, veuillez suivre la procédure décrite
dans ce document et lire attentivement les notes précédées du symbole suivant :
Le symbole suivant sera également utilisé dans ce document. Veuillez lire attentivement les notes
d'informations indiquées après ce symbole.
Connectiques
2
1
Intérieur de la coque avant
1
(modèle standard)
Modèle ambiant /
Modèles arrière, déporté et standard
(1)
(2)
Transmetteur d'humidité
et de température
90 mm
90 mm
Modèle ambiant
24.4 mm
46 mm
Ø13 mm
Ø13 mm
46 mm
90 mm
Modèle standard
4
5
3
1. Switch 1 (S1)
6
2. Switch 2 (S2)
Face avant mobile
Boîter arrière fixe
3. Connexion logiciel LCC-S
4. Bornier de sortie
5. Bornier d'alimentation
6. Presse-étoupe
4
5
3
6
90 mm