Electrode Setting; Burner Start-Up Cycle - Riello Burners F10 Manuel D'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

ELECTRODE SETTING

Attention:
Before assembling or removing the noz-
zle, loosen the screw (A) and move the
electrodes ahead.

BURNER START-UP CYCLE

Normal
Thermostat
Motor
Ignition transformer
Valve
Flame
Lock-out lamp
WARNINGS TO AVOID BURNOUT OR BAD COMBUSTION OF THE
BURNER
– When the burner is stopped, the smoke pipe must be opened and effect a natural draught in the
combustion chamber. If the smoke pipe is closed, the burner must be drawn back till the extrac-
tion of blast tube from the furnace. Before operating in this way take the voltage off.
– The place, where the burner works, must have same openings suitable for the passage of air
necessary for combustion. To be sure about this, you have to control the smoke number of
exhaust gas with all the windows and doors closed.
– If in the place, where the burner works, there are air-breathings, check the existence of air-
input openings with dimensions suitable for the necessary air-exchange. In any case check
that, when the burner is stopped, the air-breathings do not draw warm smokes from pipes
through the burner.
2359
All manuals and user guides at all-guides.com
4 ±
0.3 mm
D5288
~
12s
MOVE THE ELECTRODE
HOLDER BACKWARDS TO
THE END
A
Lock-out, due to light-failure
~
12s
6
GB
4.5 ±
0.5 mm
~
D5229
5s