Télécharger Imprimer la page

Emerson Appleton Code-Master Jr. LED CJL Instructions D'installation Et De Maintenance page 2

Publicité

Les langues disponibles

Les langues disponibles

GROUP C & D INSTALLATIONS:
Pendant and Stanchion Mounting Hoods: Remove connection block from mounting hood by loosening two (2) mounting screws.
Thread hood onto conduit at least five (5) threads (conduit should engage the internal stop) and tighten locking screw.
• Connect the green wire to the green screw provided in the mounting hood.
• Connect the black wire to the black wire of connection block, and the white wire to the white wire of
connection block.
• Replace the connection block into the mounting hood and re-tighten the screws securely.
• Screw fixture body into hood by hand until gasket makes contact with hood. Keep turning until the fixture body cannot be turned
any more and is firmly in place.
• Do not open globe ring assembly, as there are no replaceable parts inside the fixture body.
Wall Bracket and Ceiling Box Mounting Hoods: Install wall bracket or ceiling box on structural support member with four bolts
through four external mounting holes. Remove connection block and connect electrically as described above under "Pendant and
Stanchion Mounting Hoods."
Appleton • 1.800.621.1506 • www.appletonelec.com
FIGURE 2
CLASS I, DIV. 1
GROUP C, D INSTALLATIONS:
CEILING MOUNTING HOOD
CONNECTION BLOCK
COLLECTOR RING AND PIN
NAMEPLATE FOR
ELECTRICAL
SPECIFICATIONS
GLOBE RING
ASSEMBLY
GUARD
IMPORTANT
FOR CORRECT CODE CLASSIFICATION AND GROUPING,
SEE FIGURE 1.
IMPORTANT: Remove all unused
conduit plugs and reinstall with
pipe sealant.
DOUBLE LEAD
ACME THREAD
GASKET
AS FIXTURE
UNIT IS
THREADED
INTO MOUNTING
HOOD, AN
AUTOMATIC
ELECTRICAL
CONNECTION
IS MADE
650593-000 Rev. C 07/01/19 MY6381 • Page 2 of 10

Publicité

loading