Minimum thickness of the concrete pad: 100 mm.
Minimum length of the anchor bolts: 300 mm.
Minimum tensile strength of the bolts: 7.7 kN. Security coefficient 1.5.
Minimum shear strength of the bolts: 9.3 kN. Security coefficient 1.25.
Below are the dimensions of the anchors.
INGEREV FUSION Wall
The INGEREV FUSION Wall must be installed on an even, solid and completely vertical surface, taking into
account the specifications of the applicable regulations in the installation location.
22
35
150
=
=
Front of the station
Preparation for installing the unit
Back of the station
265
M12
ABW2011IQM01_D - Installation and Operation Manual