R7284B,P,U,G
Electronic Oil Primary,
EnviraCOM™ Enabled
READ BEFORE INSTALLING
APPLICATION
The R7284B,P,U,G Electronic Oil Primary is a line voltage,
safety rated, interrupted and intermittent ignition oil
primary control for residential oil fired burners used in
boilers, forced air furnaces and water heaters. The
R7284B,P,U,G used with a cad cell flame sensor operates
an oil burner, spark igniter, and optional oil valve. The
control works with a low voltage and optional high
voltage thermostat. The primary controls fuel oil, senses
flame, controls ignition spark (either interrupted or
intermittent) and notifies through the EnviraCOM™ bus a
remote alarm circuit when in lockout.
The R7284 Series of Oil Primary Controls can be used
with both hydronic and forced air systems. When used
with hydronic systems, line voltage switching
Aquastat® Controllers normally provide for the starting
and stopping of the combustion sequences. With forced
air systems, both mechanical and electronic low voltage
thermostats control the starting and stopping of the
combustion process.
Some hydronic and forced air systems require a delayed
valve-on and burner motor-off delay. The R7284
operates an oil valve that prevents the flow of oil when
the burner motor is running prior to combustion
(delayed valve-on) and when the burner motor is
running after combustion (burner motor-off delay).
The R7284 models are intended for use only on oil
burning appliances which do not require prepurge and
post-purge as a safety related function as defined in
UL296. The valve-on delay and burner motor-off delay in
this control are intended only to help establish draft and
reduce oil after-drip related problems.
EnviraCOM™ enabled R7284's can be used with
EnviraLink® remote monitoring systems and hand-held
diagnostics. Use only R7284P and U models for
networking with other EnviraCOM™ enabled devices.
FEATURES
User Interface
There are two user interfaces: basic and advanced. Both
interfaces consist of three buttons: , , and "i."
INSTALLATION INSTRUCTIONS
The advanced interface has a two-line display used to
configure device parameters, retrieve diagnostic
information, and display system status.
The basic interface has a single LED used to display
error codes and system status.
In general, the "i" button cycles through the display
options and acts as an "enter" key (in setup modes).
Thermostat(s)
The oil primaries are compatible with both standard
thermostats and EnviraCOM™ communicating
thermostats.
Limited Recycle
This feature limits the number of recycle trials (for each
call for heat) to a maximum of three trials. If the flame is
lost three times and does not successfully satisfy a call
for heat, the R7284 locks out.
Pump Priming Cycle
To facilitate purging air from the oil lines and filters, the
R7284 can be placed in a purge routine by pressing and
releasing the up arrow button during the Trial For
Ignition.
In the advanced interface "PUMP PRIME" is displayed on
the display along with the time left on the Trial for
Ignition (TFI). Pressing the up arrow button adds a
minute to the TFI time for a maximum of 10 additional
minutes (press the up arrow button 10 times). Pressing
the down arrow button subtracts a minute from the TFI
time.
There is no visual indication for the basic interface
control and the purge timing is limited to five minutes.
Disable Function
Pressing and holding the "i" button will disable all
control functions until 3 seconds after the button is
released.
69-2467EFS-11

Publicité

Table des Matières
loading

Sommaire des Matières pour resideo EnviraCOM R7284B

  • Page 1 R7284B,P,U,G Electronic Oil Primary, EnviraCOM™ Enabled INSTALLATION INSTRUCTIONS The advanced interface has a two-line display used to READ BEFORE INSTALLING configure device parameters, retrieve diagnostic information, and display system status. APPLICATION The basic interface has a single LED used to display error codes and system status.
  • Page 2 R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED Electrical Ratings: Lockout Modes Inputs: The R7284 has three types of lockout modes that are Voltage: 102 to 132 Vac, 120 Vac nominal. entered when an error is encountered: Current: 0.5A plus burner motor, valve and igniter loads.
  • Page 3 R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED Location CHECKOUT 1. Mount on a 4 in. by 4 in. junction box, directly on the main burner, or inside the appliance cabinet. In Start System replacement applications, mount in the same loca- tion as the old control. See Fig. 1. Make sure the operating temperatures are within the ambient WARNING temperature range (see Specifications section).
  • Page 4 R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED AQUASTAT® R7284B, G R7284P, U CIRCULATION CONTROLLER PUMP AQUASTAT LIMIT OR OTHER LIMIT AQUASTAT OR OTHER L8148A,C LIMIT R7284 THERMOSTAT LIMIT M32179 JUMPER Fig. 4. R7284 Limit wiring for line voltage thermostat, Aquastat, or other Limit. ENVIRACOM™...
  • Page 5 R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED T8635L C7089B OUTDOOR TEMPERATURE SENSOR TH9421C VisionPRO IAQ AQUASTAT® W8635A CONTROLLER L7224/48 R7284 LIMIT RELAY COOL 1 RELAY (HOT) SYSTEM COOL 2 ENVIRACOM™ BURNER BURNER TRANSFORMER RELAY TERMINAL MOTOR MOTOR IGNITOR IGNITOR VALVE R7284 VALVE LIMIT LIMIT...
  • Page 6: Home Screens

    R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED ADVANCED USER INTERFACE UP/DOWN ERROR HISTORY UP/DOWN (NO SELECTED) HOME SCREEN HOLD ALL 3 BUTTONS (YES SELECTED) (EXIT SELECTED) CAD CELL HISTORY (CONT. SELECTED) IGNITION TIME HISTORY INSTALLER SETUP SCREENS CYCLE COUNTS M32103A Fig. 11. User interface overview. If at any point there is an event generating a lockout, one Home Screens of the following screens will be displayed.
  • Page 7 R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED Adjustment of the Burner Off Delay. View History From the Diagnostic screen scroll to the View History Configuration of the TT terminals vs. screen and select YES. Scroll through the performance an “internal jumper.” Configure the data by using the up or down buttons.
  • Page 8: Troubleshooting And Maintenance

    R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED BASIC USER INTERFACE R7284 Error Codes (Basic Interface) The basic user interface consists of 3 buttons and an LED. Simple diagnostic information can be obtained Table 4. Error Codes. through the interaction of the buttons and LED. Number of 1/4 sec Error Codes flashes...
  • Page 9 R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED WARNING Electrical Shock Hazard. Can cause severe injury, death or property damage. Troubleshoot with the system powered. Be careful to observe all precautions to prevent electrical shock or equipment damage. Table 5. R7284 Operation. External Action R7284 Action Power applied to control.
  • Page 10 R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED Table 6. Troubleshooting Information. Condition: Burner does not start with a call for heat Procedure Control Status Corrective Action Review error history if control Refer to Error Codes table of this section in lockout Check that limit switches are Display models: display shows Replace limit switch or clean contacts.
  • Page 11: Corrective Action

    R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED Table 7. Display Alarm Information. (Continued) EnviraCOM™ Display Alarm Alarm Number Corrective Action Flame Proven • The cad cell is permanently in a low resistance state. It should typically read much higher than 20,000 ohms when no flame is present. Out of Sequence •...
  • Page 12 This product is manufactured by Resideo Technologies, Inc. and its affiliates. Tous droits réservés. Ce produit est fabriqué par Resideo Technologies, Inc. et ses sociétés affiliées. Todos los derechos reservados. Este producto es fabricado por Resideo Technologies, Inc. y sus afiliados.
  • Page 13: Régulateur Primaire À Mazout Électronique R7284B,P,U,G Compatible Enviracom

    Régulateur primaire à mazout élec- tronique R7284B,P,U,G compatible EnviraCOM™ NOTICE D'INSTALLATION Les modèles R7284 compatibles avec EnviraCOM™ LIRE AVANT L’INSTALLATION peuvent être utilisés avec les systèmes de surveillance à distance EnviraLink® et les appareils de diagnostic de poche. Utiliser uniquement les modèles R7284P et U APPLICATION pour le fonctionnement en réseau avec d'autres dispositifs compatibles EnviraCOM™.
  • Page 14: Fonction De Désactivation

    RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ flèche ascendante ajoute une minute à la durée TFI (appuyer 10 fois pour 10 minutes max. supplémentaires). Verrouillage : 15, 30 ou 45 secondes. Le fait d'appuyer sur le bouton avec touche descendante Remise en marche : 60 secondes (fixe).
  • Page 15: Emplacement

    RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ 1. Le câblage doit être conforme aux codes et aux INSTALLATION règlements locaux. 2. Vérifier que le câblage de la tension secteur est bien connecté. Consulter l'étiquette du régulateur à Lors de l'installation de ce produit... mazout et le schéma de câblage de l'appareil pour 1.
  • Page 16 RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ R7284A, G R7284B, P, U VANNE VANNE VANNE BOUTON MOTEUR DE MOTEUR DE MOTEUR DE MOTEUR DE HAUT AFFICHEUR BRÛLEUR BRÛLEUR BRÛLEUR BRÛLEUR BORNES DE MF32180 BOUTON THERMOSTAT Fig. 5. Câblage du R7284 pour vanne à mazout en option. BOUTON i BORNES ENVIRACOM...
  • Page 17 RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ CONTRÔLEUR POMPE DE AQUASTAT® CIRCULATION L8148A,C R7284 THERMOSTAT LIMITEUR TH9421C VisionPRO IAQ CAVALIER CONTRÔLEUR AQUASTAT® BORNE ENVIRACOM™ MOTEUR DE L7224/48 MOTEUR DE R7284 BRÛLEUR BRÛLEUR LIMITEUR ALLUMEUR ALLUMEUR VANNE CELLULE DE CELLULE DE BORNE MOTEUR DE MOTEUR DE...
  • Page 18 RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ IMPORTANT Le système montré à la Fig. 10 est sensible à la T8635L phase/polarité. S'assurer que toute la C7089B CAPTEUR DE puissance d'entrée est dans la même phase. TEMPÉRATURE EXTÉRIEURE W8635A RELAIS VENTI- LATEUR RELAIS...
  • Page 19: Interface Utilisateur Avancée

    RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ INTERFACE UTILISATEUR AVANCÉE HAUT/BAS ERREUR HISTORIQUE HAUT/BAS (NON SÉLECTIONNÉ) ÉCRAN D’ACCUEIL APPUYER SUR LES 3 BOUTONS (OUI SÉLECTIONNÉ) CELLULE CADMIUM (QUITTER SÉLECTIONNÉ) HISTORIQUE (SUITE SÉLECTIONNÉ) PÉRIOD ALLUMAGE ÉCRANS DE HISTORIQUE CONFIGURATION DE L’INSTALLATEUR COMPTAGE DE CYCLES MF32103A...
  • Page 20: Voir Historique

    RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ Sélectionner entre anglais, français REMARQUE : Le rétablissement des valeurs de et espagnol en utilisant les boutons référence permet d'établir de nouvelles haut et bas et le bouton « i » pour valeurs de référence pour la cellule de cadmium et la durée d'allumage.
  • Page 21: Écrans D'historique Des Erreurs

    RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ Le fait d'appuyer sur « i » au cours de tout écran de durée Description Code DEL d'allumage permet de passer aux écrans de compte de Verrouillage Clignotement de 1/2 seconde sur cycle ci-dessous.
  • Page 22: Dépannage Et Entretien

    RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ DÉPANNAGE ET ENTRETIEN Étapes préliminaires 1. Vérifier les connexions de câblage et l'alimentation. IMPORTANT 2. S'assurer que les régulateurs sont sous tension. En raison des dangers potentiels liés à l'alimen- 3. S'assurer que le limiteur est fermé. tation secteur, seul un technicien d'entretien 4.
  • Page 23 RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ Tableau 5. Fonctionnement du R7284. Action externe R7284 Action Puissance appliquée au Vérification de sécurité interne effectuée. Si aucune lumière ou flamme n'est régulateur. détectée et que toutes les conditions internes sont correctes, le régulateur passe en mode de veille.
  • Page 24 RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ Tableau 6. Informations sur le dépannage. Condition : Le brûleur ne se lance pas avec l'appel de chaleur Procédure Statut du régulateur Action corrective Revoir l'historique des Consulter le tableau des codes d'erreur dans erreurs si le régulateur est cette section verrouillé...
  • Page 25 RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ Tableau 7. Informations sur les alarmes de l'affichage. Numéro d'alarme Alarme de l'affichage EnviraCOM™ Action corrective PAS D'ALLUMAGE • Le brûleur n'était pas allumé et l'étincelle non détectée. Vérifier le bon VÉRIF. ALLUMEUR fonctionnement des électrodes, des contacts à...
  • Page 26 RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ Tableau 7. Informations sur les alarmes de l'affichage. (Continued) Numéro d'alarme Alarme de l'affichage EnviraCOM™ Action corrective DÉPASSÉ • La flamme est été perdue plus de fois que le nombre permis. Le RECYCLAGES MAX brûleur s'allume mais ne reste pas allumé.
  • Page 27 RÉGULATEUR PRIMAIRE À MAZOUT ÉLECTRONIQUE R7284B,P,U,G COMPATIBLE ENVIRACOM™ Tableau 8. Codes de clignotement DEL. Code de cligno- Numéro tement d'alarme EnviraCOM™ Action corrective 10,5,20,59,9 Le brûleur n'était pas allumé ni allumé vers la fin de l'essai d'allumage. • Vérifier que le robinet manuel est ouvert. •...
  • Page 28: Avertissement De Sécurité

    This product is manufactured by Resideo Technologies, Inc. and its affiliates. Tous droits réservés. Ce produit est fabriqué par Resideo Technologies, Inc. et ses sociétés affiliées. Todos los derechos reservados. Este producto es fabricado por Resideo Technologies, Inc. y sus afiliados.
  • Page 29: Características

    Control electrónico primario de aceite R7284B,P,U,G habilitado con EnviraCOM™ INSTRUCCIONES DE INSTALACIÓN Los controles R7284 habilitados con EnviraCOM™ LEER ANTES DE INSTALAR pueden emplearse con sistemas de monitorización a distancia y diagnósticos manuales. Use únicamente los modelos R7284P y U para interconectar con otros APLICACIÓN dispositivos habilitados con EnviraCOM™.
  • Page 30 CONTROL ELECTRÓNICO PRIMARIO DE ACEITE R7284B,P,U,G HABILITADO CON ENVIRACOM™ agregará un minuto al tiempo de TFI, con un máximo de Duración: 10 minutos adicionales (presione el botón de flecha Retardo de activación de la válvula: de 0 a 30 segundos. hacia arriba 10 veces).
  • Page 31: Encendido Del Sistema

    CONTROL ELECTRÓNICO PRIMARIO DE ACEITE R7284B,P,U,G HABILITADO CON ENVIRACOM™ 1. Asegúrese de que el cableado cumpla con todas INSTALACIÓN las ordenanzas y los códigos locales. 2. Verifique para asegurarse de que el cableado del voltaje de línea esté conectado correctamente. Cuando instale este producto...
  • Page 32 CONTROL ELECTRÓNICO PRIMARIO DE ACEITE R7284B,P,U,G HABILITADO CON ENVIRACOM™ R7284A, G R7284B, P, U VÁLVULA VÁLVULA VÁLVULA BOTÓN DE FLECHA MOTOR DEL MOTOR DEL MOTOR DEL MOTOR DEL HACIA QUEMADOR QUEMADOR QUEMADOR QUEMADOR ARRIBA PANTALLA BOTÓN DE MS32180 FLECHA TERMINALES HACIA Fig.
  • Page 33 CONTROL ELECTRÓNICO PRIMARIO DE ACEITE R7284B,P,U,G HABILITADO CON ENVIRACOM™ CONTROLADOR BOMBA DE AQUASTAT® CIRCULACIÓN L8148A,C R7284 TERMOSTATO TH9421C LIMIT VisionPRO IAQ PUENTE CONTROLADOR AQUASTAT® TERMINAL ENVIRACOM™ L7224/48 MOTOR DEL MOTOR DEL R7284 QUEMADOR QUEMADOR LÍMITE ENCENDEDOR ENCENDEDOR VÁLVULA CÉLULA TERMINAL MOTOR DEL MOTOR DEL CÉLULA...
  • Page 34 CONTROL ELECTRÓNICO PRIMARIO DE ACEITE R7284B,P,U,G HABILITADO CON ENVIRACOM™ IMPORTANTE T8635L El sistema, tal como se muestra en la Fig. 10, es sensible a la polaridad/fase. Asegúrese de que C7089B SENSOR DE toda la energía de entrada sea de la misma fase. TEMPERATURA EXTERIOR W8635A...
  • Page 35: Pantallas Principales

    CONTROL ELECTRÓNICO PRIMARIO DE ACEITE R7284B,P,U,G HABILITADO CON ENVIRACOM™ INTERFAZ DE USUARIO AVANZADA ARRIBA/ ABAJO HIST DE FALLAS ARRIBA/ ABAJO (SE SELECCIONA PANTALLA PRINCIPAL MANTENER PRESIONADOS LOS TRES BOTONES (SE SELECCIONA SÍ) (SE SELECCIONA CÉLULA CAD SALIR) HISTORIAL (SE SELECCIONA CONTINUAR) TMPO DE IGNICIÓN PANTALLAS DE...
  • Page 36 CONTROL ELECTRÓNICO PRIMARIO DE ACEITE R7284B,P,U,G HABILITADO CON ENVIRACOM™ NOTA: el tiempo de encendido puede ajustarse NOTA: el volver al punto de referencia establecerá únicamente durante los primeros 100 ciclos de nuevos valores de punto de referencia para la funcionamiento. Después de los 100 ciclos, el célula de cadmio y el tiempo de encendido que existan en adelante.
  • Page 37 CONTROL ELECTRÓNICO PRIMARIO DE ACEITE R7284B,P,U,G HABILITADO CON ENVIRACOM™ Presione “i” en cualquiera de las pantallas de tiempo de Estado del R7284 (interfaz básica) encendido para ingresar a la pantalla de conteo de ciclos que se detalla a continuación. Tabla 2. Códigos LED. Ciclos totales del quemador.
  • Page 38 CONTROL ELECTRÓNICO PRIMARIO DE ACEITE R7284B,P,U,G HABILITADO CON ENVIRACOM™ interfaz con indicador LED, durante una orden normal de Códigos de error del R7284 calefacción, una vez que el control ingresó al modo de (interfaz básica) funcionamiento, presione y suelte el botón “i”. En el modelo avanzado con pantalla, siga el Tabla 4.
  • Page 39 CONTROL ELECTRÓNICO PRIMARIO DE ACEITE R7284B,P,U,G HABILITADO CON ENVIRACOM™ Tabla 5. Funcionamiento del R7284. Acción externa Acción del R7284 Energía conectada al control. Verificación de seguridad interna realizada. Si no se detecta luz ni llama y todas las condiciones internas están bien, el control ingresa al modo de espera. Órdenes de calefacción del 1.
  • Page 40 CONTROL ELECTRÓNICO PRIMARIO DE ACEITE R7284B,P,U,G HABILITADO CON ENVIRACOM™ Tabla 6. Información para la localización y solución de problemas. Condición: el quemador no se enciende con una orden de calefacción Procedimiento Estado del control Medida correctiva Si el control está Consulte la tabla de códigos de error de esta bloqueado, revise el sección...
  • Page 41 CONTROL ELECTRÓNICO PRIMARIO DE ACEITE R7284B,P,U,G HABILITADO CON ENVIRACOM™ Tabla 7. Información sobre la alarma de la pantalla. Número de alarmas Alarma de la pantalla EnviraCOM™ Medida correctiva No hay ignición • El quemador no se encendió y no se detectaron chispas. Verifique el Revisar Ign.
  • Page 42 CONTROL ELECTRÓNICO PRIMARIO DE ACEITE R7284B,P,U,G HABILITADO CON ENVIRACOM™ Tabla 7. Información sobre la alarma de la pantalla. (Continued) Número de alarmas Alarma de la pantalla EnviraCOM™ Medida correctiva Excedidos • La llama se apagó más veces que lo permitido. El quemador se enciende, Reciclados máx pero no permanece encendido.
  • Page 43 CONTROL ELECTRÓNICO PRIMARIO DE ACEITE R7284B,P,U,G HABILITADO CON ENVIRACOM™ Tabla 8. Códigos de destello del indicador LED. Código de destello Número de alarmas indicador EnviraCOM™ Medida correctiva 10,5,20,59,9 El quemador no se encendió o lo hizo casi al final del tiempo de prueba. •...
  • Page 44: Advertencia De Seguridad

    This product is manufactured by Resideo Technologies, Inc. and its affiliates. Tous droits réservés. Ce produit est fabriqué par Resideo Technologies, Inc. et ses sociétés affiliées. Todos los derechos reservados. Este producto es fabricado por Resideo Technologies, Inc. y sus afiliados.

Ce manuel est également adapté pour:

Enviracom r7284pEnviracom r7284uEnviracom r7284g

Table des Matières