R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED
BASIC USER INTERFACE
The basic user interface consists of 3 buttons and an
LED. Simple diagnostic information can be obtained
through the interaction of the buttons and LED.
R7284 Status (Basic Interface)
Table 2. LED Codes.
Description
Standby
Pulse (1/4 sec. ON, 4 sec OFF)
Call for Heat
Heartbeat (1/2 sec bright, 1/2 sec dim)
Flame proven
On solid
Recycle
2 second ON, 2 second OFF flashing
Lockout
1/2 second on, 1/2 second OFF flashing
Interrupt
OFF
"i" button
Flame Strength Indication
Up button
Most recent error
Down button
Next most recent error
R7284 Flame Strength
(Basic Interface)
During normal operation and when the R7284 is in the
Running state, the LED will show CAD cell resistance. See
Table 3.
Table 3. Flame Strength Indication.
Flame Strength Indication
Cad Cell less than 400Ω
400Ω < Cad Cell < 800Ω
800Ω < Cad Cell < 1600Ω
1600Ω < Cad Cell < 6100Ω
Cad Cell > 6100Ω
Error History (Basic Interface)
The last two errors are available for display on the LED:
• Pressing the up arrow button displays the most recent
error.
• Pressing the down arrow button displays the next
most recent error.
Once the up or down arrow is pushed, the LED will display
the most recent or next most recent alarm by blinking the
error code. See Table 4.
69-2467EFS—11
LED Code
Number of 1/2 sec flashes
1
2
3
4
None
R7284 Error Codes
(Basic Interface)
Table 4. Error Codes.
Error Codes
No ignition / Late ignition
Max flame losses / Cad Cell high while
running
Flame out of sequence
Low Voltage / EnviraCOM™ error
Internal Error
TROUBLESHOOTING AND
MAINTENANCE
IMPORTANT
Due to the potential hazard of line voltage, only
a trained, experienced service technician should
preform the troubleshooting procedures.
This control contains no field-serviceable parts.
Do not attempt to take it apart. Replace entire
control if operation is not as described.
To completely troubleshoot an oil burner installation,
check the burner and oil primary control for proper
operation and condition.
Cad Cell Resistance Check
For proper operation, it is important that the cad cell
resistance is below 1600 ohms. On the basic model with
LED interface, during a normal call for heat, once the
control has entered the Run mode, press and release the
"i" button.
On the advanced model with display, follow the screen
diagnostic procedure to read the cad cell resistance.
Cad cell resistance can be checked without using an ohm
meter.
Preliminary Steps
1. Check wiring connections and power supply.
2. Make sure power is on to controls.
3. Make sure limit control is closed.
4. Check contacts between igniter and the electrodes.
5. Check the oil pump pressure.
6. Check the piping to the oil tank.
7. Check the oil nozzle, oil supply and oil filter.
Check Oil Primary Control
If the trouble is not in the burner or ignition hardware,
check the oil primary control by using the following
equipment:
1. Screwdriver.
2. Voltmeter (0 to 150 Vac range).
3. Insulated jumper wire with both ends stripped.
8
Number of 1/4 sec
flashes
1
2
3
4
5