Braukmann
FK06 DialSet®
LOW LEAD PRESSURE REGULATING FILTER COMBINATION
FK06-101-DUS-LF, FK06-101-DUT-LF, FK06-102-DUS-LF, FK06-102-DUT-LF, FK06-103-DUS-LF, FK06-103-DUT-LF
READ BEFORE INSTALLING
SAFETY GUIDELINES
1. Follow the installation instructions.
2. Use and install the appliance
• according to its intended use
• in good condition
• with due regard to safety and risk of danger,
according to local codes and standards.
3. Note that the appliance is exclusively for use in the
applications detailed in these installation instructions.
Any other use will not be considered to comply with
requirements and would invalidate the warranty.
4. Please take note that any assembly, commissioning,
servicing and adjustment work may only be carried out
by authorized persons.
5. Immediately rectify any malfunctions which may influ-
ence safety.
DESCRIPTION OF FUNCTION
The filter combination integrates a pressure reducing valve
and a rinsable fine filter cartridge in one appliance.
During normal operation, water flows through the filter mesh
to the body outlet. To rinse the filter, the ball valve is opened
which discharges the dirt particles. A continous supply of
filtered water is available also during the rinse cycle.
The integral pressure reducing valve functions on a balanced
force principle whereby the force exerted by a diaphragm is
balanced against the force of an adjustment spring. The inlet
pressure has no influence on opening or closing of the valve.
Inlet pressure fluctuation does not therefore affect the outlet
pressure.
APPLICATION
Medium: Water
Inlet pressure: 250 psi (17.24 bar)
Outlet pressure: 25–90 psi (1.5–6 bar)
The filter is constructed for drinking water installations. In
case of a process water application the filter has to be proven
individually.
M36611A
TECHNICAL DATA
Installation position: horizontal with filter bowl downward
Operating pressure: 250 psi (17.24 bar)
Operating temperature: 104°F (40°C)
Connection size: 3/4" (19 mm), 1" (25.4 mm), 1-1/4"
(31.7 mm)
SCOPE OF DELIVERY
The filter combination consists of:
• Housing with pressure gauge connections on both sides
• Threaded or sweat connections, based on model
• Valve insert complete with diaphragm and valve seat
• Spring bonnet with setting knob and scale
• Adjustment spring
• Fine filter in clear filter bowl
• Ball valve
INSTALLATION INSTRUCTIONS
WARNING
Install indoors only. Do not use in applications where
UV radiation and solvent vapors are present.
38-00059EFS-05