R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED
ADVANCED USER INTERFACE
(YES SELECTED)
Home Screens
Pressing the "i" button longer than 2 seconds in states
other than Standby Interrupts control operation.
Once the held key is released the count down begins.
• Holding all 3 buttons longer than 2 seconds in any
state goes to Installer Setup (ISU).
• Pressing "i" in any state enters the Diagnostic screen
(if diagnostics are enabled).
• Pressing up or down in any screen enters Error History
(if diagnostics are enabled).
Below is a typical progression of screens through a
normal cycle.
Pressing up or down during the
Ignition Trial enters pump prime.
Each press of the up button adds a
minute, each press of the down
button subtracts a minute from the
pump prime time.
69-2467EFS—11
i
i
i
i
(NO SELECTED)
i
CAD CELL HISTORY
i
i
(CONT. SELECTED)
IGNITION TIME
HISTORY
i
CYCLE COUNTS
Fig. 11. User interface overview.
ERROR HISTORY
UP/DOWN
i
HOME SCREEN
i
HOLD ALL
3 BUTTONS
(EXIT SELECTED)
i
i
INSTALLER SETUP
SCREENS
i
If at any point there is an event generating a lockout, one
of the following screens will be displayed.
Installer Setup
Installer setup is entered by pushing all three buttons
simultaneously for 2 seconds.
NOTE:
Not all parameters are adjustable in all models.
Parameters not available for adjustment will
display "Locked" when an attempt is made to
modify them.
NOTE:
The Ignition Time is only available for adjust-
ment during the first 100 cycles of operation.
After 100 cycles the Ignition Time is locked in
and can no longer be adjusted.
6
UP/DOWN
i
M32103A
Control is in Soft Lockout. Control
will recover when error clears or after
specified time.
Control is in Hard Lockout. Hold "i"
for at least 2 seconds to reset.
Hold the "i" button longer than 10
seconds to return to Standby.
If QUIT is selected, an "i" button
press displays the Re-baseline
option.
If CONT is selected, an "i" button
press goes to "Installer Setup".
Select between English, French, or
Spanish by using the up or down
buttons and the "i" button to select
Adjustment of the Valve On Delay in
five second increments.
Ignition (lockout) Time adjustment.