25 ACCESSING DATA ShEET

Select change in the MENU and turn to OK to confirm.
Select data sheet in the CHANGE menu and turn
to OK to confirm.
valve tag number
Select valve tag number to read or write valve ID.
Use the blue selector to change the first character and turn to
OK to confirm.
Change remaining characters using the same method.
Turn to OK when all of the characters have been entered and
continue until the menu is displayed again.
actuator number: this is the actuator's serial number. This information
is entered at the factory and is only shown in the CHECK menu.
entry code: for entering or changing a password, see below:
"Creating or changing passwords".
characteristics: parameter settings for correct operation of the
actuator (see details next page).
The following data is only shown in the CHECK menu.
operating class: indicates whether the actuator is designed for
on/off operation, class III control or class II control functions. This
item can be used to activate an alarm if the number of starts
is excessive (excess. starts alarm).
The number is the counted over the previous 12-hour period.
Limits are as follows:
On / Off:
360 starts in previous 12 hours
Class III:
1,200 starts in previous 12 hours
Class II:
21,600 starts in previous 12 hours
This alarms never causes the actuator to stop operating.
manufacture date: gives date product shipped from factory software version: installed software
release
Characteristics menu details
motor : this data indicates whether the motor has a 3-phase, single phase or DC
power supply (data from manufacturer)
protection: waterproof or explosion-proof version. The explosion-proof version prevents overriding
the thermal relay in the degraded mode/commands menu.
locked motor/s: Indicates the time the motor left energised when immobilised before power cut off.
Default: 10 seconds (manufacturer's data)
reverse delay/ms: Indicates time actuator halted following change in direction of rotation.
Default: 200 ms (manufacturer's data).
ratio position system: indication of gear stepdown ratio between output shaft and position sensor
for displaying stroke in number of revolutions (or in degrees for fractions of a revolution) (manufactu-
rer's data).
28
To check settings without making
changes, select check instead
of change in the menu.
DATA SHEET
return
valve tag number
actuator number
entry code
operating class
manufacture date
characteritics
software version
return
VALVE TAG NUMBER
MOV55VV
CHARACTERITICS
return
motor
locked motor/s
reverse delay/ms
ratio position system
ext gear ratio 1/
thread mm
stroke
return
external gear ratio 1/: indication of gear stepdown ratio for an additional gear. For example, for a
quarter-turn gear with a ratio of 1:120, enter 120.
Travel will then be indicated in degrees.
thread in mm: Indication of pitch of a linear system to allow travel to be displayed in mm, rather
than in number of revolutions
stroke: Indication of stroke value measured when adjusting valve.

26 CREATING OR ChANGING PASSWORD

Select change in the MENU turn to OK to confirm.
Select data sheet in the CHANGE menu and turn to OK to confirm.
Select entry code in the DATA SHEET menu and turn to OK to confirm.
Enter 1st digit with the blue button, then turn to OK to confirm.
Enter 2nd digit with the blue button, then turn to OK to confirm.
Enter 3rd digit with the blue button, then turn to OK to confirm.
The new code will not be taken into account until the user exits
the change menu and confirms the change (change ok?)
Make sure you can remember this code to access the change menu again.
If you forget your code
Switch off power to the system unit and open the control unity to access
the INTELLI+ board (supporting the display). Move the jumper on the board
from position A to position B, then turn the power back on. The password
has now been reset to zero. Place the jumper back in its original position
(A).
If you leave the jumper in position B, you will still be able to enter a new
password, but it will be reset to zero the next time you switch the unit on.

27 USING ANALOGUE POSITION SIGNAL (DEPENDING ON MODEL)

On some models, the actuator can use an analogue signal to transmit its percentage position (0 -
100%) to a remote device.
The output signals are automatically calibrated on the actuator's stroke (0 - 100%) and so the trans-
mitted position signal does not need any adjustment.
The transmitted signals are totally isolated from the
INTELLI+ circuits.
Use a rectified, filtered or stabilised 12 - 32V DC
power supply for this position signal. It is also possible
to use the internal 24V power supply on terminals
6(-) and 7(+).
Max. permissible loading is shown on the table.
The following signals can be used:
4-20 mA, 0-20 mA, 4-12 mA or 12-20 mA.
4-20 mA, 4-12 mA or 12-20 mA outputs can connected
with two wires, with the external power supply in series
with the signal reading. (see actuator circuit diagram)
The 0-20 mA output can be used to obtain a 0-10V
signal using an external 500 ohm (or 499 ohm 1%)
resistor.
The power supply voltage will be 15 to 32V.
ENTRY CODE
(000)
CAV
A
B
jumper
Power supply
Max. permissible
(volts)
load (ohms)
12
150
34
750
30
1050
+
32
+
33
15 - 32V
-
500
34
0-10V
Ohm
-
35
0-10V position remote signal
29