Page 1
® in any orientation and does exactly what you need it to do. La gamme de pompes BlueDiamond dépasse les performances d’autres pompes de ® condensation, peut être montée dans n’importe quelle orientation et fait exactement ce que vous attendez d’elle.
Page 2
• In the box • Dans la boîte • Material suministrado • Mounting detail • Notice de montage • Acerca del montaje • Continuous running option • Option fonctionnement continu MINIBLUE MAXIBLUE MAXIBLUE MEGABLUE ® ® ® ® • Opción de funcionamiento continuo •...
Page 4
Caution: Alarm lead must be connected to a class 2 circuit only –Do not connect to a load higher than 5A, 240v AC/DC. Caution: This pump has been evaluated for use with water only. Caution: Risk of electric shock: This pump has not been investigated for use in swimming pool or marine areas.
Page 5
A CONTINUÉ..Avertissement: La pompe ne doit pas être placée à l’extérieur, immergée dans l’eau ou exposée au gel. Avertissement: Tous les éléments de récupération existants et des installations doivent être nettoyés à fond avant l’installation. N’installez endommagé. Avertissement: Convient pour une utilisation intérieure seulement. Cuidado: El cable del alarma se debe conectar sólo a un circuíto de la clase 2 - no conectar a un circuito con una carga mayor a 5A, 240V AC/DC.
Page 6
• Any modifications to the unit will immediately void the warranty. • We reserve the right to alter specifications without prior notice. La série de pompes BlueDiamond® est fabriquée sous le contrôle d’un système de qualité très stricte de Charles Austen Pumps. Dans le cas peu probable d’une panne dans les 2 ans suivant la date d’achat dans des conditions d’utilisation normale,...
Page 7
1. Pump (MINIBLUE, MAXIBLUE or MEGABLUE) 2. 2m (6’ 7”) mains lead 3. Zero volt alarm lead (Reservoir and DrainStik only) ® 4. Sensor input socket 5. Sensing Option (A) Reservoir OR (B) Hot & cold sensor OR (C) DrainStik ®...
Page 8
MEGABLUE 9.21 ® MAXIBLUE 5.59 ® MINIBLUE 4.80 ® The pump may be mounted in any orientation but must be kept dry. La pompe peut être montée dans n’importe quelle orientation, mais doit être gardée sèche. La bomba se puede montar en cualquier orientación, pero se ha de mantener en seco.
Page 9
*Fuse pumps 0.5A (Not Supplied) FLOW HEAD (A) LIFT (B) MINIBLUE 2.1 G/HR 23 FEET 16.5 FEET 0.5A ® MAXIBLUE 3.7 G/HR 23 FEET 16.5 FEET 0.5A ® MEGABLUE 13.2 G/HR 66.5 FEET 23 FEET 1.0A ® Leave sufficient space around the pump unit to allow for cooling. Ensure that the pump is not more than A above the condensate outlet, and not more than B below the desired drainage point for the pump outlet.
Page 10
El depósito dispone de un tubo de evacuación de aire , cuyo extremo abierto debe estar a un nivel superior que el depósito. Asegúrese de que el depósito está en posición HORIZONTAL y bien fijado mediante los tornillos suministrados. MINIBLUE MAXIBLUE MAXIBLUE MEGABLUE ®...
Page 11
INDOOR OUTDOOR UNIT UNIT PUMP CONNECTIONS GREEN WHITE OPTIMAL BLACK 0.5A YELLOW BLACK The alarm circuit is only applicable to product using the Reservoir and DrainStik sensing options. NC (Yellow) / NO (Red) and C (Black) will not operate when using the Temperature Sensing option C21-013...
Page 12
Inserte el sensor en la manguera de la bandeja de condensados como indicado y coloque y fije la manguera en su posición. El DrainStik de ha de montar de ® forma vertical. Utilice la manguera de silicona suministrada. MINIBLUE MAXIBLUE MAXIBLUE MEGABLUE ®...
Page 13
INDOOR OUTDOOR UNIT UNIT PUMP CONNECTIONS GREEN WHITE OPTIMAL BLACK 0.5A YELLOW BLACK The alarm circuit is only applicable to product using the Reservoir and DrainStik sensing options. NC (Yellow) / NO (Red) and C (Black) will not operate when using the Temperature Sensing option STEP ADAPTER: S12-004...
Page 14
Para eso se recomienda no utilizar falsos techos, porque normalmente hay temperaturas más altas. Coloque el sensor del termistor frío (Azul ) v en el caudal de aire de la unidad de aire acondicionado. MINIBLUE MAXIBLUE MAXIBLUE MEGABLUE ®...
Page 15
INDOOR OUTDOOR UNIT UNIT PUMP CONNECTIONS GREEN WHITE OPTIMAL BLACK 0.5A YELLOW BLACK The alarm circuit is only applicable to product using the Reservoir and DrainStik sensing options. NC (Yellow) / NO (Red) and C (Black) will not operate when using the Temperature Sensing option.
Page 16
The continuous running (cooling signal) option allows the pump to run continuously. If powered from the same source as the A/C Unit, it will switch on / off with the A/C Unit. Connect the plug into the Sensor Input Socket before installation. *The CR plug is a sensing option and is not included with standard pumps.
Page 17
The water test ensures that the pump responds to the water level & that the pump switches off when dry. To test, slowly pour cold water into the tray until the pump switches on. Allow the pump to run and switch off.The pump should run for approximately 7 seconds after emptying the reservoir/condensate tray pipe.
Page 18
To ensure that the alarm connection is working, restrict the outlet of the reservoir hose and fill with water up to the high level sensor. The pump will turn on intially, then after a short delay the alarm relay will switch which can be detected using a multimeter or observing the shut down of the AC unit.
Page 19
If the pump is installed remotely, occasionally water can become trapped in the u-bend at the lowest point of the system. Due to the pump’s high flow rate, this can create a gurgling noise.It is recommended to fit the silencer supplied with the hot &...