CPs MODE :
The airflow of the fan is automatically regulated to maintain a pressure sensor's value constant.
4) Configuration
Configuration of the fan is made using the LCD display and the 4 setup knobs. SETUP,
To start the configuration press SETUP until SETUP text appear on the LCD.
The principle of selection is to use keys ↑and ↓ to make the choice and to press ENTER to confirm. The numbers
are introduced figure by figure.
Below you will find a simplified configuration for the use with only one fan.
Complete information is available on the website :
1
LANGUAGE
2
DISPLAY m³h ?
3
DISPLAY Pa ?
4
DISPLAY m/s?
5
TYPE VEN
6
# FAN?
7
MODE
If MODE CA
8
m³h K1?
9
m³h K2?
10
m³h K3?
If MODE LS
8
V min?
9
V max?
10
m³/h≡Vmin
11
m³/h≡Vmin
12
% on K3?
NEXT if MODE CA or LS
CONFIG
13
TIME? N
TIME
14
SEGMENT ?N
PRESSURE
15
ALARM?
∆P FAN
16
17
INIT Pa REF?
18
m³h INIT
Pa REF INIT
19
xxxx m³h
xxxx Pa
20
END SETUP
If MODE CPf or CPs
8
% on K3?
CONFIG
9
TIME? N
TIME
10
SEGMENT ?N
11
INIT CP REF?
INIT via
12
AIRFLOW?
www.swegon.com
Language choice
If yes, the airflow of each fan will be displayed on the screen
If yes, the pressure of each fan will be displayed on the screen
If yes, the air speed of each fan will be displayed on the screen (Fill in surface in m²)
Choice of fan through (CID – see label on fan)
Select number of fans connected to CB (F1 or F1+F2).
Choice of working mode (CA, LS, CPf, CPs)
Select Airflow 1 for each F1,F2 fan (contacts between terminals K1 and +12V closed)
Select Airflow 2 for each F1,F2 fan (contacts between terminals K2 and +12V closed)
Select Airflow 3 for each F1,F2 fan (contacts between terminals K3 and +12V closed)
Select minimum voltage value for LS link
Select maximum voltage value for LS link
Select airflow for each F1,F2 fan corresponding to Vmin
Select airflow for each F1,F2 fan corresponding to Vmax
Select multiplier of airflow when terminals +12V and K3 are closed ('night' setup).
Select Y to configure time and date
Select Y to activate the time segment scheduling function
Complete information is available on the website :
Pressure alarm is optional. If you do not wish to set a pressure alarm select N(o),
otherwise select Y(es)
If you have selected Y: Configuration of pressure alarm on fan:
Select value of pressure increment corresponding to the nominal airflow.
Configuration of pressure alarm: Do you wish to (re)define the nominal pressure
corresponding to a new nominal airflow ?
If you have selected Y: Pressure alarm setup. Enter airflow to define reference
pressure.
Initialisation of the reference pressure busy. After 1 minute the CB will memorize the
value of the calculated static pressure on the fan once the INIT airflow is reached.
Display of instant value of airflow and pressure while initializing .
The setup is then completed.
Select multiplier for CPf or CPs resulting airflow when terminals +12V and K3 are closed
('night' setup).
Select Y to configure time and date
Select Y to activate the time segment scheduling function
Complete information is available on the website :
Setup of CPf or CPs fan pressure instruction ?
Define if the constant pressure assignment value (Pa or V) for the fans:
- is to be automatically determined as a consequence of a selected airflow value
- is to be typed in by the user: select PRESSURE
www.swegon.com
12
,
and ENTER.
www.swegon.com